H5-14, H5-15: BACnet Device Object Identifiers 0 and 1

Note:

These parameters are ignored when N2 protocol is selected (H5-08 = 1).

These parameters set the Instance Identifier of the BACnet Device Object, where the H5-14 value is the least significant word

and the H5-15 value is the most significant word.

No.

Name

Setting Range

Default

H5-14

BACnet Device Object Identifier 0

0 to FFFFH

1

H5-15

BACnet Device Object Identifier 1

0 to 3FH

0

Example 1: Set Device Object Instance Identifier of “1234”
1234 decimal is equal to 4D2H (hexadecimal)
Set H5-14 to 4D2H and set H5-15 to 0.
Example 2: Set Device Object Instance Identifier of “1234567”
12334567 decimal is equal to 12D687H
Set H5-14 to D687H and set H5-15 to 12H.

D.4 N2 Setup Parameters

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

291

D

Metasys N2 Communications