beautypg.com

Analog input objects, Analog output objects, Analog value objects – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 257

background image

Property

Object Type

Device

Analog

Input

Analog

Output

Analog

Value

Binary

Output

Binary

Output

Binary

Value

Inactive_Text

Yes

Yes

Yes

Active_Text

Yes

Yes

Yes

<1> For Commandable Object Instances only.

u

Analog Input Objects

Table B.5 Analog Input Objects

Object ID

Object Name

Modbus

Address

Precision

Range

Units

PV Access

AI1

Analog Input 1 Level

004EH

XXXX.X

%

R

AI2

Analog Input 2 Level

004FH

XXXX.X

%

R

AI3

Not used

AI4

Not used

AI5

Not used

AI6

Display Format o1-03

0502H

XXXXX

R

AI7

Scale Format b5-20

01E2H

XXXXX

R

AI8

Inverter Model o2-04

0508F

XXXXX

R

AI9

Rated Current n9-01

05D0H

XXXX.X

Amps

R

u

Analog Output Objects

Table B.6 Analog Output Objects

Object ID

Object Name

Modbus

Address

Precision

Range

Units

PV Access

AO1

Analog Output 1 Level

0007H

XXXX.X

0 to 100.0

%

C

AO2

Analog Output 2 Level

0008H

XXXX.X

0 to 100.0

%

C

u

Analog Value Objects

Table B.7 Analog Value Objects

Object ID

Object Name

Modbus

Address

Precision

Range

Units

PV Access

AV1

Not used

AV2

Frequency Command

0002H

XXX.XX

Depends on

o1-03

0.00 to 600.00

Hz

Depends on

o1-03

C

AV3

PI Setpoint

0006H

XXX.XX

0.00 to 100.00

%

C

AV4

Not used

AV5

Not used

AV6

Not used

AV7

Not used

AV8

Not used

AV9

Frequency Reference

0040H

XXX.XX

Depends on

o1-03

Hz

Depends on

o1-03

R

AV10

Output Frequency

0041H

XXX.XX

Depends on

o1-03

Hz

Depends on

o1-03

R

AV11

Output Voltage

0045H

XXXX.X

Volts

R

B.7 BACnet Objects Supported

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

257

B

BACnet Communications