Point

Numb

er

Point

Type

Point Name

Factory

Default

(SI

Units)

Eng. Units

(SI Units)

Slope

(SI

Units)

Intercept

(SI Units)

On Text

Off Text

Parameter

78

LDI

MF IN 4 MON

OFF

1

0

ON

OFF

U1-10 (Bit 5)

79

LAI

PID DEVIATE

0

%

0.01

0

U5-02

80

LAO

PID I LIMIT

100

%

0.1

0

b5-04

81

LAO

PID UP LIMIT

100

%

0.1

0

b5-06

82

LAO

PID OFFS ADJ

100

%

0.1

-100

b5-07

83

LAO

PID PRI DYTM

0

s

0.1

0

b5-08

84

LAO

PID FB RMDS

0

1

0

b5-12

85

LAO

PID FB RMDL

0

%

1

0

b5-13

86

LAO

PID FB RMDT

1

s

0.1

0

b5-14

87

LAI

PID OUT CAP

0

%

0.01

0

U5-14

88

LAI

PID REF

0

%

0.01

0

U5-04

89

LAI

COMM ERR CD

0

1

0

U1-19

90

LDO

COMM FLT

ENA

ENABLE

1

0

ENABL

E

DISABLE

H5-05

91

LAO

CBL LOSS FRQ

0

Hz

0.01

0

d1-04

92

LAO

CBL LOSS TMR

2

s

0.1

0

H5-09

93

LDI

OK.FAULT

OK

1

0

FAULT

OK

U1-12 (Bit 7)

94

LDO

RESET FAULT

NO

1

0

RESET

NO

95

LDI

DRV COMM

ERR

NO FLT

1

0

FAULT

NO FLT

96

LDO

EXTERNAL FLT

OK

1

0

FAULT

OK

97

LDI

MF IN 5 MON

OFF

1

0

ON

OFF

U1-10 (Bit 6)

99

LAI

ERROR

STATUS

0

1

0

U1-19

<1> Set H1-03 to 70 , Drive Enable2, for pt 35 to work properly.

C.5 APOGEE FLN Point Database

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

277

C

APOGEE FLN (P1) Communications