Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 108

background image

No.

Name

Setting Range

Default

L3-06

Stall Prevention Level During Run

30 to 150

<1>

<1>

<1> The upper limit and default for this setting is determined by L8-38.

n

L3-23: Automatic Reduction Selection for Stall Prevention during Run

Reduces the Stall Prevention during run level in the constant power range.

No.

Name

Setting Range

Default

L3-23

Automatic Reduction Selection for Stall Prevention During Run

0, 1

0

Setting 0: Disabled

The level set in L3-06 is used throughout the entire speed range.

Setting 1: Enabled

The Stall Prevention level during run is reduced in the constant power range. The lower limit will be 40% of L3-06.

n

Overvoltage Suppression Function

Suppresses overvoltage faults by decreasing the regenerative torque limit and slightly increasing the output frequency when

the DC bus voltage rises.
The regenerative torque limit and the output frequency are adjusted during ov suppression so that the DC bus voltage does

not exceed the level set to parameter L3-17. In addition to the parameters explained below, ov suppression also uses these

settings for frequency adjustment:
• DC bus voltage gain (L3-20)
• Deceleration rate calculations gain (L3-21)
• Inertia calculations for motor acceleration time (L3-24)
• Load inertia ratio (L3-25)

Note:

1. The motor speed will exceed the frequency reference when overvoltage suppression is triggered. Consequently, overvoltage suppression

is not appropriate in applications that require a perfect match between the frequency reference and the motor speed.

2. Overvoltage may still occur if there is a sudden increase to a regenerative load.
3. This function is enabled only when operating just below the maximum frequency. Overvoltage suppression does not increase the output

frequency beyond the maximum frequency. If the application requires this, increase the maximum frequency and change the base

frequency setting.

n

L3-11: Overvoltage Suppression Function Selection

Enables or disables the overvoltage suppression function.

No.

Name

Setting Range

Default

L3-11

Overvoltage Suppression Function Selection

0, 1

0

Setting 0: Disabled

The regenerative torque limit and the output frequency are not adjusted. A regenerative load may trip the drive with an

overvoltage fault. Use this setting if dynamic braking options are installed.

Setting 1: Enabled

When the DC bus voltage rises due to regenerative load, an overvoltage fault is prevented by decreasing the regenerative

torque limit and increasing the output frequency.

n

L3-17: Target DC Bus Voltage for Overvoltage Suppression and Stall Prevention

Sets the target DC bus voltage level used by the overvoltage suppression function (L3-11 = 1), Intelligent Stall Prevention

during deceleration (L3-04 = 2).

No.

Name

Setting Range

Default

L3-17

Target DC Bus Voltage for Overvoltage Suppression

and Stall Prevention

431.3 to 1150 Vdc

1063.8 Vdc

<1>

<1> This value is initialized when E1-01 is changed.

1.8 L: Protection Functions

108

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual