Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 28

background image

Min output

frequency

100%

(Max output

frequency)

Output frequency

when Stop command

was entered

Run wait time t

Active deceleration time

Min Baseblock Time (L2-03)

Figure 1.7 Run Wait Time Depending on Output Frequency

n

b1-04: Reverse Operation Selection

Enables and disables Reverse operation. For some applications, reverse motor rotation is not appropriate and may cause

problems (e.g., air handling units, pumps, etc.).

No.

Parameter Name

Setting Range

Default

b1-04

Reverse Operation Selection

0, 1

1

Setting 0: Reverse Enabled

Possible to operate the motor in both forward and reverse directions.

Setting 1: Reverse Disabled

Drive disregards a Reverse run command or a negative frequency reference.

n

b1-08: Run Command Selection in Programming Mode

As a safety precaution, the drive will not normally respond to a Run command input when the HOA keypad is being used to

adjust parameters in Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and Auto-Tuning Mode). If

required by the application, set b1-08 to allow the drive to run while in Programming Mode.

No.

Parameter Name

Setting Range

Default

b1-08

Run Command Selection in Programming Mode

0 to 2

0

Setting 0: Run Command Is Not Accepted in Programming Mode

A Run command is not accepted while the HOA keypad is in Programming Mode.

Setting 1: Run Command Is Accepted in Programming Mode

A Run command is accepted in any HOA keypad mode.

Setting 2: Prohibit Entering Programming Mode during Run

It is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot be

displayed during Run.

n

b1-11: Drive Delay Time Setting

If a time is set to b1-11, the drive will delay executing a Run command until the set time has expired. During Drive Delay

Time execution, the HOA keypad will display “WrUn”. Both Alarm and Run indicators will blink while the drive waits to

execute the Run command.

No.

Parameter Name

Setting Range

Default

b1-11

Drive Delay Time Setting

0 to 600 s

0

n

b1-14: Phase Order Selection

Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Switching motor phases will reverse the direction of the motor.

No.

Parameter Name

Setting Range

Default

b1-14

Phase Order Selection

0, 1

0

1.2 b: Application

28

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual