Page 143: S3-17: secondary pi feedback detection selection

background image

S3-13

PI2 Low Feedback

Detection Level

PI2 Feedback

(U5-18)

S3-15

PI2 High Feedback

Detection Level

On-delay

Timer

On-delay

Timer

S3-16

PI2 High Feedback

Detection Time

S3-14

PI2 Low Feedback

Detection Time

PI2 disabled

S3-17 = 0

False

True

False

True

Multi-function output

H2-oo = 71

PI2 Feedback Low

Multi-function output

H2-oo = 72

PI2 Feedback Low

+

-

+

-

Figure 1.76 PI Low Feedback Detection Level

n

S3-14: Secondary PI Low Feedback Detection Time

Sets the secondary PI low feedback detection delay time in seconds.

No.

Name

Setting Range

Default

S3-14

Secondary PI Low Feedback Detection Time

0.0 to 25.5 s

1.0 s

n

S3-15: Secondary PI High Feedback Level

Sets the secondary PI high feedback detection level.

No.

Name

Setting Range

Default

S3-15

Secondary PI High Feedback Level

0.00 to 600.00

<1>

300.0

<2>

<1> Upper limit is S3-02, decimal place holder is determined by S3-03.
<2> Unit is determined by S3-04.

n

S3-16: Secondary PI High Feedback Detection Time

Sets the secondary PI high feedback detection delay time in seconds.

No.

Name

Setting Range

Default

S3-16

Secondary PI High Feedback Detection Time

0.0 to 25.5 s

1.0 s

n

S3-17: Secondary PI Feedback Detection Selection

Selects when secondary PI controller low and high feedback detection is active.

No.

Name

Setting Range

Default

S3-17

Secondary PI Feedback Detection Selection

0 or 1

0

Setting 0: Secondary PI Enabled
Setting 1: Always

1.11 S: Special Parameters

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

143

1

Parameter Details