Sequence Timer 3
Run at d1-03
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
Mon
Sun
Sat
Fri
Thur
Wed
Tue
Sequence Timer 1
Run at d1-01
Sequence Timer 2
Run at d1-02 with PI control disabled
Figure 1.74 Sequence Timer Example 3
n
S2-01/S2-06/S2-11/S2-16: Sequence Timers 1 to 4 Start Time
Sets the start times for timers 1 to 4. The values must be set less than or equal to S2-02/S2-07/S2-12/S2-17.
No.
Name
Setting Range
Default
S2-01
Sequence Timer 1 Start Time
00:00 to 24:00
00:00
S2-06
Sequence Timer 2 Start Time
00:00 to 24:00
00:00
S2-11
Sequence Timer 3 Start Time
00:00 to 24:00
00:00
S2-16
Sequence Timer 4 Start Time
00:00 to 24:00
00:00
n
S2-02/S2-07/S2-12/S2-17: Sequence Timers 1 to 4 Stop Time
Sets the stop times for timers 1 to 4. The values must be set greater than or equal to S2-01/S2-06/S2-11/S2-16.
No.
Name
Setting Range
Default
S2-02
Sequence Timer 1 Stop Time
00:00 to 24:00
00:00
S2-07
Sequence Timer 2 Stop Time
00:00 to 24:00
00:00
S2-12
Sequence Timer 3 Stop Time
00:00 to 24:00
00:00
S2-17
Sequence Timer 4 Stop Time
00:00 to 24:00
00:00
1.11 S: Special Parameters
138
YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual