Sequence Timer 3

Run at d1-03

10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00

Mon

Sun

Sat

Fri

Thur

Wed

Tue

Sequence Timer 1

Run at d1-01

Sequence Timer 2

Run at d1-02 with PI control disabled

Figure 1.74 Sequence Timer Example 3

n

S2-01/S2-06/S2-11/S2-16: Sequence Timers 1 to 4 Start Time

Sets the start times for timers 1 to 4. The values must be set less than or equal to S2-02/S2-07/S2-12/S2-17.

No.

Name

Setting Range

Default

S2-01

Sequence Timer 1 Start Time

00:00 to 24:00

00:00

S2-06

Sequence Timer 2 Start Time

00:00 to 24:00

00:00

S2-11

Sequence Timer 3 Start Time

00:00 to 24:00

00:00

S2-16

Sequence Timer 4 Start Time

00:00 to 24:00

00:00

n

S2-02/S2-07/S2-12/S2-17: Sequence Timers 1 to 4 Stop Time

Sets the stop times for timers 1 to 4. The values must be set greater than or equal to S2-01/S2-06/S2-11/S2-16.

No.

Name

Setting Range

Default

S2-02

Sequence Timer 1 Stop Time

00:00 to 24:00

00:00

S2-07

Sequence Timer 2 Stop Time

00:00 to 24:00

00:00

S2-12

Sequence Timer 3 Stop Time

00:00 to 24:00

00:00

S2-17

Sequence Timer 4 Stop Time

00:00 to 24:00

00:00

1.11 S: Special Parameters

138

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual