H2: multi-function digital outputs – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 82

background image

Setting AC: PI2 Integral Hold

Locks the value of the secondary PI controller integral value.

Setting AD: Select PI2 Parameters

Uses the secondary PI controller Proportional and Integral adjustments (S3-06 and S3-07) instead of the primary PI controller

Proportional and Integral adjustments (b5-02 and b5-03). Only valid when S3-01 = 0 (secondary PI controller disabled).

Note:

This multi-function input has no effect on the secondary PI controller. It is only used for the primary PI controller (b5-oo).

Setting AE: BP Bypass Run

Commands a Run in Bypass mode via closing the BP Bypass Relay multi-function output.

Setting AF: Emergency Override Forward Run

Enables Emergency Override Forward Run.

Setting B0: Emergency Override Reverse Run

Enables Emergency Override Reverse Run.

Setting B1: Customer Safeties

The Customer Safeties multi-function input functionality is identical to Bypass Drive Enable (Setting 70: Drive Enable 2),

except for the following:
• When the input is open, the stopping method is forced to Coast to Stop
• If the input is open when the Run command is present, a “SAFE” alarm is displayed instead of the “dnE” alarm.

Setting B2: BAS Interlock

The BAS Interlock multi-function input is used in a damper interlock circuit to keep the drive from running until the damper

control relay is closed.
• When the input is open, the drive output is shut off (baseblocked).
• The drive will display an “inTLK” message if the input is open and a Run command is present. It will not display “dnE”.
• The state of the BAS Interlock multi-function input has no effect on the Emergency Override multi-function inputs

(H1-oo = AF, B0). The Emergency Override command will be accepted if the BAS Interlock digital input is open or closed.

u

H2: Multi-Function Digital Outputs

n

H2-01 to H2-03: Terminal M1-M2, M3-M4, and M5-M6 Function Selection

The drive has three multi-function output terminals.

Table 1.29

lists the functions available for theses terminals using H2-01,

H2-02, and H2-03.

No.

Parameter Name

Setting Range

Default

H2-01

Terminal M1-M2 Function Selection (relay)

0 to 1B2

0: During Run

H2-02

Terminal M3-M4 Function Selection (relay)

0 to 1B2

1: Zero Speed

H2-03

Terminal M5-M6 Function Selection (relay)

0 to 1B2

2: Speed Agree 1

Table 1.29 Multi-Function Digital Output Terminal Settings

Setting

Function

Page

0

During Run

83

1

Zero Speed

83

2

Speed Agree 1

84

3

User-Set Speed Agree 1

84

4

Frequency Detection 1

84

5

Frequency Detection 2

85

6

Drive Ready

85

7

DC Bus Undervoltage

86

8

During Baseblock (N.O.)

86

9

Frequency Reference Source

86

Setting

Function

Page

A

Run Command Source

86

B

Torque Detection 1 (N.O.)

86

C

Frequency Reference Loss

86

E

Fault

86

F

Through Mode

86

10

Minor Fault

86

11

Fault Reset Command Active

87

12

Timer Output

87

13

Speed Agree 2

87

14

User-Set Speed Agree 2

87

1.7 H: Terminal Functions

82