beautypg.com

Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 134

background image

n

o4-11: U2, U3 Initialization

Resets the fault trace and fault history monitors (U2-oo and U3-oo). Initializing the drive using A1-03 does not reset these

monitors.

No.

Name

Setting Range

Default

o4-11

U2, U3 Initialization

0, 1

0

Setting 0: No Action

The drive keeps the previously saved record concerning fault trace and fault history.

Setting 1: Reset Fault Data

Resets the data for the U2-oo and U3-oo monitors. Setting o4-11 to 1 and pressing the ENTER key erases fault data and

returns the display to 0.

n

o4-12: kWh Monitor Initialization

Manually resets kWh monitors U4-10 and U4-11. Initializing the drive or cycling the power will not reset these monitors.

No.

Name

Setting Range

Default

o4-12

kWh Monitor Initialization

0, 1

0

Setting 0: No Action

The kWh data are maintained.

Setting 1: Reset kWh Data

Resets the kWh counter. The monitors U4-10 and U4-11 will display “0” after they are initialized. Setting o4-12 to 1 and

pressing the ENTER erases kWh data and returns the display to 0.

n

o4-13: Number of Run Commands Counter Initialization

Resets the Run command counter displayed in U4-02. Initializing the drive or cycling the power does not reset this monitor.

No.

Name

Setting Range

Default

o4-13

Number of Run Commands Counter Initialization

0, 1

0

Setting 0: No Action

The Run command data are kept.

Setting 1: Number of Run Commands Counter

Resets the Run command counter. The monitor U4-02 will show 0. Setting o4-13 to 1 and pressing the ENTER key erases the

counter value and returns the display to 0.

n

o4-17: Set/Reset Real Time Clock

The time setting screen will appear.

No.

(Addr.

Hex)

LCD Display

Name

Description

Values

o4-17

(3100)

Set Time

0: — —

1: Set

2: Reset

Set/Reset Real Time

Clock

Sets the current date and time for the Real Time Clock.

0: — — No Setting

1: Real Time Clock Set

2: Real Time Clock Reset

Default: 0

Range: 0 to 2

Setting 0: — —

No Setting

Setting 1: Set

The HOA keypad shows the Clock Adjustment display. In Clock Adjustment Mode the user can adjust the Real Time Clock.

Setting 2: Reset

The Real-Time Clock data is cleared. A TIM fault will occur until o4-17 is set to 1 to set the Real Time Clock.

1.10 o: Operator-Related Settings

134

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual