PI feedback value

PI

Feedback

Detection

Loss Level

(b5-13)

PI Feedback

Loss Detection Time

(b5-14)

No FbL
detection

FbL detection

Time

PI Feedback

Loss Detection Time

(b5-14)

Figure 1.17 PI Feedback Loss Detection

n

b5-12: PI Feedback Loss Detection Selection

Enables or disables the feedback loss detection and sets the operation when a feedback loss is detected.

No.

Parameter Name

Setting Range

Default

b5-12

PI Feedback Loss Detection Selection

0 to 5

0

Setting 0: Digital Output Only (Remains active when PI is disabled by digital input)

A digital output set for “PI feedback low” (H2-oo = 3E) will be triggered if the PI feedback value is below the detection

level set to b5-13 for the time set to b5-14 or longer. A digital output set for “PI feedback high” (H2-oo = 3F) will be triggered

if the PI feedback value is beyond the detection level set to b5-36 for longer than the time set to b5-37. Neither a fault nor an

alarm is displayed on the HOA keypad and the drive will continue operation. The output resets when the feedback value leaves

the loss detection range. Detection remains active when PI is disabled by digital input (H1-oo = 19).

Setting 1: Feedback Loss Alarm (Remains active when PI is disabled by digital input)

If the PI feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FBL - Feedback Low” alarm

will be displayed and a digital output set for “PI feedback low” (H2-oo = 3E) will be triggered. If the PI feedback value

exceeds the level set to b5-36 for longer than the time set to b5-37, a “FBH - Feedback High” alarm will be displayed and a

digital output set for “PI feedback high” (H2-oo = 3F) will be triggered. Both events trigger an alarm output (H1-oo = 10).

The drive will continue operation. The alarm and outputs reset when the feedback value leaves the loss detection range.

Detection remains active when PI is disabled by digital input (H1-oo = 19).

Setting 2: Feedback Loss Fault (Remains active when PI is disabled by digital input)

If the PI feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FbL - Feedback Low” fault

will be displayed. If the PI feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FbH - Feedback

High” fault will be displayed. Both events trigger a fault output (H1-oo = E) and cause the drive to stop the motor. Detection

remains active when PI is disabled by digital input (H1-oo = 19).

Setting 3: Digital Output Only

A digital output set for “PI feedback low” (H2-oo = 3E) will be triggered if the PI feedback value is below the detection

level set to b5-13 for the time set to b5-14 or longer. A digital output set for “PI feedback high” (H2-oo = 3F) will be triggered

if the PI feedback value is beyond the detection level set to b5-36 for longer than the time set to b5-37. Neither a fault nor an

alarm is displayed on the HOA keypad and the drive will continue operation. The output resets when the feedback value leaves

the loss detection range. Detection is disabled when PI is disabled by digital input (H1-oo = 19).

Setting 4: Feedback Loss Alarm

If the PI feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FBL - Feedback Low” alarm

will be displayed and a digital output set for “PI feedback low” (H2-oo = 3E) will be triggered. If the PI feedback value

exceeds the level set to b5-36 for longer than the time set to b5-37, a “FBH - Feedback High” alarm will be displayed and a

digital output set for “PI feedback high” (H2-oo = 3F) will be triggered. Both events trigger an alarm output (H1-oo = 10).

The drive will continue operation. The alarm and outputs reset when the feedback value leaves the loss detection range.

Detection is disabled when PI is disabled by digital input (H1-oo = 19).

1.2 b: Application

42