1.13 U: Monitor Parameters

Monitor parameters let the user view various aspects of drive performance using the HOA keypad display. Some monitors

can be output from terminals FM and AM by assigning the specific monitor parameter number (Uo-oo) to H4-01 and H4-04.

Refer to H4-01, H4-04: Multi-Function Analog Output Terminal FM, AM Monitor Selection on page 96

for details on

assigning functions to an analog output.

u

U1: Operation Status Monitors

Status monitors display drive status data such as output frequency and output current.

Refer to U1: Operation Status

Monitors on page 232

for a complete list of U1-oo monitors and descriptions.

u

U2: Fault Trace

Use these monitor parameters to view the status of various drive aspects when a fault occurs.
This information is helpful for determining the cause of a fault.

Refer to U2: Fault Trace on page 233

for a complete list of

U2-oo monitors and descriptions.
U2-oo monitors are not reset when the drive is initialized.

Refer to o4-11: U2, U3 Initialization on page 134

for instructions

on how to reset these monitor values.

Note:

Fault histories are not kept when CPF00, CPF01, CPF06, CPF24, oFA00, oFb00, oFC00, Uv1, Uv2, or Uv3 occur.

u

U3: Fault History

These parameters display faults that have occurred during operation as well as the drive operation time when those faults

occurred.

Refer to U3: Fault History on page 234

for a complete list of U3-oo monitors and descriptions.

U3-oo monitors are not reset when the drive is initialized.

Refer to o4-11: U2, U3 Initialization on page 134

for instructions

on how to reset these monitor values.

Note:

Fault histories are not kept when CPF00, CPF01, CPF06, CPF24, oFA00, oFb00, oFC00, Uv1, Uv2, or Uv3 occur.

u

U4: Maintenance Monitors

Maintenance monitors show:
• Runtime data of the drive and cooling fans and number of Run commands issued
• Maintenance data and replacement information for various drive components
• kWh data
• Highest peak current that has occurred and output frequency at the time the peak current occurred
• Motor overload status information
• Detailed information about the present Run command and frequency reference source selection

Refer to U4: Maintenance Monitors on page 236

for a complete list of U4-oo monitors and descriptions.

u

U5: PI Monitors

These monitors display various aspects of PI control.

Refer to PI Block Diagram on page 39

for details on how these monitors

display PI data.

Refer to U5: PI Monitors on page 237

for a complete list of U5-oo monitors and descriptions.

u

U6: Operation Status Monitors

These monitors display reference data for the output voltage and vector control and the offset value added to the frequency

reference by the frequency offset function.

Refer to Settings 44, 45, and 46: Offset Frequency 1, 2, 3 on page 79

for details.

Refer to U6: Operation Status Monitors on page 238

for a complete list of U6-oo monitors and descriptions.

1.13 U: Monitor Parameters

158

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual