C4: torque compensation – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 53

background image

C2-02

C2-01

0.20 s

<1>

0.20 s

<1>

C2-02

C2-01

0.20 s

<1>

0.20 s

<1>

FWD run

REV run

Output
frequency

<1> S-Curve characteristic at Decel Start/End is fixed to 0.20 s.

Figure 1.21 S-Curve Timing Diagram - FWD/REV Operation

Setting the S-curve will increase the acceleration and deceleration times.
Actual accel time = accel time setting + (C2-01 + C2-02) / 2

u

C4: Torque Compensation

The torque compensation function compensates for insufficient torque production at start-up or when a load is applied.

Note:

Set the motor parameters and V/f pattern properly before setting torque compensation parameters.

n

C4-01: Torque Compensation Gain

Sets the gain for the torque compensation function.

No.

Parameter Name

Setting Range

Default

C4-01

Torque Compensation Gain

0.00 to 2.50

Determined by

A1-02

Torque Compensation in V/f and OLV/PM:

The drive calculates the motor primary voltage loss using the output current and the termination resistor value (E2-05 for IM

motors, E5-05 for PM motors) and adjusts the output voltage to compensate insufficient torque at start or when load is applied.

The effects of this voltage compensation can be increased or decreased using parameter C4-01.

Adjustment

Although this parameter rarely needs to be changed, it may be necessary to adjust the torque compensation gain in small steps

of 0.05 in the following situations:
• Increase this setting when using a long motor cable.
• Decrease this setting when motor oscillation occurs.
Adjust C4-01 so the output current does not exceed the drive rated current.

Note:

Refrain from adjusting this parameter in OLV/PM. Setting this value too high can cause overcompensation and motor oscillation.

n

C4-02: Torque Compensation Primary Delay Time

Sets the delay time used for applying torque compensation.

No.

Parameter Name

Setting Range

Default

C4-02

Torque Compensation Primary Delay Time

0 to 60000 ms

Determined by

A1-02 and o2-04

Adjustment

Although C4-02 rarely needs to be changed, adjustments may be necessary in the following situations:
• Increase this setting if the motor vibrates.
• Decrease this setting if the motor responds too slowly to changes in the load.

1.3 C: Tuning

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

53

1

Parameter Details