O3: copy function – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 132

background image

n

o2-06: Operation Selection when HOA Keypad is Disconnected

Determines whether the drive will stop when the HOA keypad is removed in HAND mode or when b1-02 or b1-16 is set to

0. When the operator is reconnected, the display will indicate that it was disconnected.

No.

Name

Setting Range

Default

o2-06

Operation Selection when HOA Keypad is Disconnected

0, 1

1

Setting 0: Continue Operation

The operation continues.

Setting 1: Trigger a Fault

The operation stops and triggers an oPr fault. The motor coasts to stop.

n

o2-07: Motor Direction at Power Up when Using Operator

Determines the direction the motor will rotate after the drive is powered up and the Run command is given from the HOA

keypad.

Note:

This parameter is effective only when the Run command is set to be given from the HOA keypad (b1-02, b1-16 = 0).

No.

Name

Setting Range

Default

o2-07

Motor Direction at Power Up when Using Operator

0, 1

0

Setting 0: Forward
Setting 1: Reverse

n

o2-19: Selection of Parameter Write during Uv

Selects whether parameter settings can be changed during a DC bus undervoltage condition. Used with 24 V Power Supply

option (PS-A10LB, PS-A10HB).

No.

Name

Setting Range

Default

o2-19

Selection of Parameter Write during Uv

0, 1

0

Setting 0: Disabled
Setting 1: Enabled

u

o3: Copy Function

These parameters control the Copy function of the HOA keypad. The Copy function stores parameter settings into the memory

of the HOA keypad to facilitate the transfer of those settings to other drives that are the same model, capacity, and same control

mode setting.

n

o3-01: Copy Function Selection

Instructs the drive to Read, Write, or Verify parameter settings.

No.

Name

Setting Range

Default

o3-01

Copy Function Selection

0 to 3

0

Setting 0: Copy Select (No Function)
Setting 1: INV --> OP READ

Copies all parameters from the drive to the HOA keypad.

Note:

The copy protection for the HOA keypad is enabled by default. Set o3-01 to 1 to unlock copy protection.

Setting 2: OP --> INV WRITE

Copies all parameters from the HOA keypad to the drive.

Setting 3: OP<-->INV VERIFY

Compares the parameters in the drive with the parameter settings saved on the HOA keypad for matches.

1.10 o: Operator-Related Settings

132

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual