Fwd Run

Drive Enable-Customer

Safeties

Override (Smoke Purge)

Drive/Bypass Select

BP Drive Relay Contact

Output

BAS Interlock

BP Bypass Relay Contact

Output

BP BAS Interlock Contact

Output

Output Frequency

Drive Fault

Bypass Run

L2-03

L2-03

Drive

Fault

Occurs

Drive

Fault

Cleared

Speed

Search

Occurs

Figure 1.80 Transfer on Fault

Energy Savings Mode

When the BP Energy Save Bypass Trigger Level (S4-02) is greater than 0, the Energy Savings Mode is enabled. If the drive

is running at a speed, as determined by SFS output equal to or greater than Maximum Output Frequency minus BP Energy

Save Bypass Trigger Level (E1-04 - S4-02) for the time specified in BP Energy Save Bypass Timer (S4-03), the drive output

frequency ramps to Maximum Output Frequency plus BP Energy Save Bypass Speed Increase (E1-04 + S4-04).
When the SFS output frequency is equal to Maximum Output Frequency plus BP Energy Save Bypass Speed Increase (E1-04

+ S4-04), the drive will perform an immediate transfer to bypass.

Refer to Immediate Transfer to Bypass on page 144

for

details.
The drive will continue to run on line voltage until the frequency command drops below E1-04 - S4-02 (Maximum Output

Frequency minus BP Energy Save Bypass Trigger Level). When this occurs, the drive performs the switch.

Refer to Transfer

to Drive Operation on page 144

for details.

The BP BAS Interlock Open message will display when the drive is waiting for the BAS feedback before issuing an internal

Run command or closing the BP Bypass Relay Contact.

1.11 S: Special Parameters

148