Output Frequency

C1-11

Accel/Decel Time

Switch Frequency

C1-03

setting

When the output frequency C1-11, drive uses Accel/Decel Time 1 (C1-01, -02)
When the output frequency < C1-11, drive uses Accel/Decel Time 2 (C1-03, -04)

C1-01

setting

C1-02

setting

C1-04

setting

Figure 1.20 Accel/Decel Time Switching Frequency

n

C1-11: Accel/Decel Time Switching Frequency

Sets the frequency at which the drive switches between accel/decel time settings.

Refer to Switching Accel/Decel Times by

a Frequency Level on page 51

for details.

No.

Parameter Name

Setting Range

Default

C1-11

Accel/Decel Time Switching Frequency

0.0 to 240.0 Hz

0.0 Hz

Note:

Setting C1-11 to 0.0 disables this function.

n

C1-09: Fast Stop Time

Sets a special deceleration used when a select group of faults occur or when closing a digital input configured as H1-oo =

15 (N.O. input) or 17 (N.C. input). A momentary closure of the digital input will trigger the Fast Stop operation; it does not

have to be closed continuously.
The drive cannot be restarted after initiating a Fast Stop operation until after completing deceleration, clearing the Fast Stop

input, and cycling the Run command.
A digital output programmed for “During Fast Stop” (H2-oo = 4C) will be closed as long as Fast Stop is active.

No.

Parameter Name

Setting Range

Default

C1-09

Fast Stop Time

0.1 to 6000.0 s

10.0 s

NOTICE: Rapid deceleration can trigger an overvoltage fault. The drive output shuts off when faulted and the motor coasts. Set an

appropriate Fast Stop time to C1-09 to avoid this uncontrolled motor state and to ensure that the motor stops quickly and safely.

u

C2: S-Curve Characteristics

Use S-curve characteristics to smooth acceleration and deceleration and minimize abrupt shock to the load. Set S-curve

characteristic time during acceleration/deceleration at start and acceleration/deceleration at stop. Increase the value set to

C2-01 if the STo fault (Step Out Detection) occurs when starting a PM motor.

n

C2-01 and C2-02: S-Curve Characteristics

C2-01 and C2-02 set separate S-curves for each section of the acceleration or deceleration.

No.

Parameter Name

Setting Range

Default

C2-01

S-Curve Characteristic at Accel Start

0.00 to 10.00 s

Determined by

A1-02

C2-02

S-Curve Characteristic at Accel End

0.20 s

Figure 1.21

illustrates S-curve application.

1.3 C: Tuning

52