E5: pm motor settings – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 68

background image

• B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.
• F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the test report at 115 °C.

Set the Motor Iron Loss for Torque Compensation

Only required when using V/f Control. Enter this value in watts to E2-10. The drive uses this setting to improve the precision

of torque compensation.

u

E5: PM Motor Settings

These parameters set the motor data of a PM motor.
Perform Auto-Tuning for PM motors. The motor data can be entered manually, if known.

Note:

1. E5-oo parameters are visible only when a OLV/PM motor control mode is selected (A1-02 = 5).
2. E5-oo parameters are not reset when the drive is initialized using parameter A1-03.

n

E5-02: Motor Rated Power

Sets the rated power of the motor. Determined by the value set to T2-04 during Stationary Auto-Tuning for PM motors.

No.

Parameter Name

Setting Range

Default

E5-02

Motor Rated Power

0.10 to 370.00 kW

Determined by

o2-04

n

E5-03: Motor Rated Current

Sets the motor rated current in amps. Automatically set when the value is entered to T2-06 during Auto-Tuning.

No.

Parameter Name

Setting Range

Default

E5-03

Motor Rated Current

10 to 200% of drive rated

current

Determined by

o2-04

Note:

Display is in the following units: 5A0007 to 5A0017: 0.01 A units; 5A0022 to 5A0242: 0.1 A units.

n

E5-04: Number of Motor Poles

Sets the number of motor poles. Automatically set when the value is entered to T2-08 during Auto-Tuning.

No.

Parameter Name

Setting Range

Default

E5-04

Number of Motor Poles

2 to 48

Determined by

o2-04

n

E5-05: Motor Stator Resistance (r1)

Set the resistance for one motor phase. Do not enter the line-to-line resistance into E5-05 when measuring the resistance

manually.

No.

Parameter Name

Setting Range

Default

E5-05

Motor Stator Resistance

0.000 to 65.000 Ω

Determined by

o2-04

n

E5-06: Motor d-Axis Inductance (Ld)

Sets the d-Axis inductance in 0.01 mH units.

No.

Parameter Name

Setting Range

Default

E5-06

Motor d-Axis Inductance

0.00 to 300.00 mH

Determined by

o2-04

n

E5-07: Motor q-Axis Inductance (Lq)

Sets the q-Axis inductance in 0.01 mH units.

1.5 E: Motor Parameters

68

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual