Alarm Outputs for Maintenance Monitors

An output can be set up to inform the user when a specific components has neared its expected performance life.
When one of multi-function digital output terminals has been assigned the maintenance monitor function (H2-oo = 2F), the

terminal will close when the cooling fan, DC bus capacitors, or DC bus pre-charge relay reach 90% of the expected performance

life, or when the IGBTs have reached 50% of their expected performance life. Additionally the HOA keypad will display an

alarm like shown in

Table 2.5

to indicate the specific components that may need maintenance.

Table 2.5 Maintenance Alarms

HOA Keypad Alarm Display

Function

Corrective Action

<1>

LT-1

The cooling fans have reached 90% of their designated

life time.

Replace the cooling fan.

<1>

LT-2

The DC bus capacitors have reached 90% of their

designated life time.

Contact a Yaskawa representative or the

nearest Yaskawa sales office on

possible drive replacement.

<1>

LT-3

The DC bus charge circuit has reached 90% of its

designated life time.

Contact a Yaskawa representative or the

nearest Yaskawa sales office on

possible drive replacement.

<1> This alarm message will be output only if the Maintenance Monitor function is assigned to one of the digital outputs (H2-oo = 2F). The alarm

will also trigger a digital output that is programmed for alarm indication (H2-oo = 10).

<2> This alarm message will always be output, even if the Maintenance Monitor function is not assigned to any of the digital outputs (H2-oo = 2F).

The alarm will also trigger a digital output that is programmed for alarm indication (H2-oo = 10).

n

Related Drive Parameters

Use parameters o4-03, o4-05, o4-07, and o4-09 to reset a Maintenance Monitor to zero after replacing a specific component.

Refer to Parameter List on page 183

for details on parameter settings.

NOTICE: If these parameters are not reset after the corresponding parts have been replaced, the Maintenance Monitor function will continue

to count down the performance life from the value that was reached with the old part. If the Maintenance Monitor is not reset, the drive will

not have the correct value of the performance life for the new component.