A.17 V/f Pattern Default Values

The following tables show the V/f pattern setting default values depending on the control mode (A1-02) and the V/f pattern

selection (E1-03 in V/f Control).

Table A.4 E1-03 V/f Pattern Settings for Drive Capacity: 5A0003 to 5A0009

No.

Unit

V/f Control

E1-03

-

0

1

2

3

4

5

6

7

8

9

A

B

C

D

E

F

<1>

E1-04

Hz

50.0

60.0

60.0

72.0

50.0

50.0

60.0

60.0

50.0

50.0

60.0

60.0

90.0

120.0

180.0

60.0

E1-05

V

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

E1-06

Hz

50.0

60.0

50.0

60.0

50.0

50.0

60.0

60.0

50.0

50.0

60.0

60.0

60.0

60.0

60.0

60.0

E1-07

Hz

2.5

3.0

3.0

3.0

25.0

25.0

30.0

30.0

2.5

2.5

3.0

3.0

3.0

3.0

3.0

3.0

E1-08

V

43.1

43.1

43.1

43.1

100.6

143.8

100.6

143.8

54.6

69.0

54.6

69.0

43.1

43.1

43.1

43.1

E1-09

Hz

1.3

1.5

1.5

1.5

1.3

1.3

1.5

1.5

1.3

1.3

1.5

1.5

1.5

1.5

1.5

1.5

E1-10

V

25.9

25.9

25.9

25.9

23.0

25.9

23.0

25.9

31.6

37.4

31.6

43.1

25.9

25.9

25.9

25.9

<1> This value determines the default values for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).

Table A.5 E1-03 V/f Pattern Settings for Drive Capacity: 5A0011 to 5A0077

No.

Unit

V/f Control

E1-03

-

0

1

2

3

4

5

6

7

8

9

A

B

C

D

E

F

<1>

E1-04

Hz

50.0

60.0

60.0

72.0

50.0

50.0

60.0

60.0

50.0

50.0

60.0

60.0

90.0

120.0

180.0

60.0

E1-05

V

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

E1-06

Hz

50.0

60.0

50.0

60.0

50.0

50.0

60.0

60.0

50.0

50.0

60.0

60.0

60.0

60.0

60.0

60.0

E1-07

Hz

2.5

3.0

3.0

3.0

25.0

25.0

30.0

30.0

2.5

2.5

3.0

3.0

3.0

3.0

3.0

3.0

E1-08

V

40.3

40.3

40.3

40.3

100.6

143.8

100.6

143.8

51.8

67.0

51.8

67.0

40.3

40.3

40.3

40.3

E1-09

Hz

1.3

1.5

1.5

1.5

1.3

1.3

1.5

1.5

1.3

1.3

1.5

1.5

1.5

1.5

1.5

1.5

E1-10

V

20.1

20.1

20.1

20.1

17.3

20.1

17.3

20.1

25.9

31.6

25.9

37.4

20.1

20.1

20.1

20.1

<1> This value determines the default values for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).

Table A.6 E1-03 V/f Pattern Settings for Drive Capacity: 5A0099 to 5A0242

No.

Unit

V/f Control

E1-03

-

0

1

2

3

4

5

6

7

8

9

A

B

C

D

E

F

<1>

E1-04

Hz

50.0

60.0

60.0

72.0

50.0

50.0

60.0

60.0

50.0

50.0

60.0

60.0

90.0

120.0

180.0

60.0

E1-05

V

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

575.0

E1-06

Hz

50.0

60.0

50.0

60.0

50.0

50.0

60.0

60.0

50.0

50.0

60.0

60.0

60.0

60.0

60.0

60.0

E1-07

Hz

2.5

3.0

3.0

3.0

25.0

25.0

30.0

30.0

2.5

2.5

3.0

3.0

3.0

3.0

3.0

3.0

E1-08

V

34.5

34.5

34.5

34.5

100.6

143.8

100.6

50.0

43.1

57.5

43.1

57.5

34.5

34.5

34.5

34.5

E1-09

Hz

1.3

1.5

1.5

1.5

1.3

1.3

1.5

1.5

1.3

1.3

1.5

1.5

1.5

1.5

1.5

1.5

E1-10

V

17.3

17.3

17.3

17.3

14.4

17.3

14.4

17.3

20.1

25.9

20.1

31.6

17.3

17.3

17.3

17.3

<1> This value determines the default values for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).

A.17 V/f Pattern Default Values

240