S2-03/S2-08/S2-13/S2-18: Sequence Timers 1 to 4 Day Selection

Sets the days for which sequence timers 1 to 4 are active.

No.

Name

Setting Range

Default

S2-03

Sequence Timer 1 Day Selection

0 to 10

0

S2-08

Sequence Timer 2 Day Selection

0 to 10

0

S2-13

Sequence Timer 3 Day Selection

0 to 10

0

S2-18

Sequence Timer 4 Day Selection

0 to 10

0

Setting 0: Timer Disabled
Setting 1: Daily
Setting 2: Mon - Fri
Setting 3: Sat - Sun
Setting 4: Monday
Setting 5: Tuesday
Setting 6: Wednesday
Setting 7: Thursday
Setting 8: Friday
Setting 9: Saturday
Setting 10: Sunday

n

S2-04/S2-09/S2-14/S2-19: Sequence Timers 1/2/3/4 Selection

Sets the action that occurs when sequence timers 1 to 4 are active.

No.

Name

Setting Range

Default

S2-04

Sequence Timer 1 Selection

0 to 2

0

S2-09

Sequence Timer 2 Selection

0 to 2

0

S2-14

Sequence Timer 3 Selection

0 to 2

0

S2-19

Sequence Timer 4 Selection

0 to 2

0

Setting 0: Digital Output Only
Setting 1: Run
Setting 2: Run - PI Disable

n

S2-05/S2-10/S2-15/S2-20: Sequence Timers 1/2/3/4 Reference Source

Selects the frequency reference source used for running the drive when sequence timers 1 to 4 are active (only applicable when

S2-04/S2-09/S2-14/S2-19 are set to 1 or 2).

No.

Name

Setting Range

Default

S2-05

Sequence Timer 1 Reference Source

0 to 6

0

S2-10

Sequence Timer 2 Reference Source

0 to 6

0

S2-15

Sequence Timer 3 Reference Source

0 to 6

0

S2-20

Sequence Timer 4 Reference Source

0 to 6

0

1.11 S: Special Parameters

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

139

1

Parameter Details