Page 24: B1-01: frequency reference selection for auto mode

background image

1.2 b: Application

u

b1: Operation Mode Selection

n

b1-01: Frequency Reference Selection for AUTO Mode

Selects the frequency reference source 1.

Note:

If a Run command is input to the drive, but the frequency reference entered is 0 or below the minimum frequency, the AUTO or HAND

indicator LED on the HOA keypad will light and the OFF indicator will flash.

No.

Parameter Name

Setting Range

Default

b1-01

Frequency Reference Selection for AUTO Mode

0 to 3

1

Setting 0: HOA Keypad

Using this setting, the frequency reference can be input by:
• switching between the multi-speed references from d1-01 to d1-04.
• entering the frequency reference on the operator keypad.

Setting 1: Terminals (Analog Input Terminals)

Using this setting, an analog frequency reference can be entered as a voltage or current signal from terminals A1 or A2.
Voltage Input
Voltage input can be used at any of the two analog input terminals. Make the settings as described in

Table 1.5

for the input

used.

Table 1.5 Analog Input Settings for Frequency Reference Using Voltage Signals

Terminal

Signal Level

Parameter Settings

Notes

Signal Level

Selection

Function Selection

Gain

Bias

A1

0 to 10 V

with Zero Limit

H3-01 = 0

H3-02 = 0

(Frequency Reference Bias)

H3-03

H3-04

Set Jumper S1 on the terminal

board to “V” for voltage input.

0 to 10 V

without Zero

Limit

H3-01 = 1

A2

0 to 10 V

with Zero Limit

H3-09 = 0

H3-10 = 0

(Frequency Reference Bias)

H3-11

H3-12

0 to 10 V

without Zero

Limit

H3-09 = 1

Drive

A1 Analog Input 1

0 to 10 V

AC Analog input common

2 k

+V 10.5 V, 20 mA power supply

A2 Analog Input 2

V

I

A1 A2

Jumper S1
Terminal A1/A2
Voltage/Current
Selection

V

I

A1 A2

Figure 1.1 Setting the Frequency Reference as a Voltage Signal at Terminal A1

Use the wiring example shown in

Figure 1.1

for any other analog input terminals. When using input terminals A1 and A2,

make sure Jumper S1 is set for voltage input.