Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 90

background image

ON

ON

OFF

OFF

ON

OFF

ON

run command

baseblock

command

output

frequency

during run

during frequency

output

OFF

Figure 1.49 During Frequency Output Time Chart

Setting 38: Drive Enable

Reflects the status of a digital input configured as a “Drive enable” input (H1-oo = 6A). If that digital input closes, then the

digital output set for “Drive enable” will also close.

Setting 39: Watt Hour Pulse Output

Outputs a pulse to indicate the watt hours.

Setting 3A: Drive Overheat Alarm (oH2)

Output closes when an external device triggers an overheat warning in the drive.

Setting 3D: During Speed Search

The output terminal closes while Speed Search is being performed.

Refer to b3: Speed Search on page 31

for details.

Setting 3E: PID Feedback Low

The output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it falls below the

level set to b5-13 for longer than the time set to b5-14.

Refer to PI Feedback Loss Detection on page 41

for details.

Setting 3F: PID Feedback High

The output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it rises beyond the

level set to b5-36 for longer than the time set to b5-37.

Refer to PI Feedback Loss Detection on page 41

for details.

Setting 4A: During KEB Operation

The output terminal closes while KEB is being performed.

Setting 4B: During Short Circuit Braking

The output terminal closes while Short Circuit Braking is being executed.

Setting 4C: During Fast Stop

The output terminal closes when a Fast Stop is being executed.

Refer to Settings 15 and 17: Fast Stop (N.O., N.C.) on page

76

.

Setting 4D: oH Pre-Alarm Time Limit

The output terminal closes when the drive is reducing the speed due to a drive overheat alarm (L8-03 = 4) and the overheat

alarm has not disappeared after 10 frequency reduction operation cycles.

Refer to L8-03: Overheat Pre-Alarm Operation

Selection on page 117

for a more detailed description.

Setting 50: Waiting to Run (WrUn)

The drive will delay executing a Run command until the time set to b1-11 has expired.

Setting 51: Sequence Timer 1 Active

Sequence Timer 1 is active.

1.7 H: Terminal Functions

90

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual