beautypg.com

Recommended cable – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 272

background image

u

Recommended Cable

Table C.2 APOGEE FLN Cable Specifications

Secification

Description

Cable configuration

Twisted shielded pair

Gauge

Stranded wire: 0.2 to 1.0 mm

2

(24 to 16 AWG)

Sold wire: 0.2 to 1.5 mm

2

(24 to 16 AWG)

Wire lay

Minimum 6 twists per foot

Shields

100% foil with drain wire

NEC type

UL type CMP

Temperature

-10 °C to +40 °C IP20/NEMA Type 1 Enclosure, External Heatsink

-10 °C to +50 °C IP00/Open Type Enclosure

Note:

Cable lengths cannot exceed 152 m (500 feet) at 4800 baud.

C.3 Connecting to a Network

272

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual