Fwd Run

Drive Enable-Customer

Safeties

Override (Smoke Purge)

Drive/Bypass Select

BP Drive Relay Contact

Output

BAS Interlock

BP Bypass Relay Contact

Output

BP BAS Interlock Contact

Output

SFS Output Frequency

L2-03

S4-03

BP Energy Save
Bypass Timer

<1>

<2>

<1> E1-04 minus S4-02 (BP Energy Save Bypass Trigger Level)
<2> E1-04 plus S4-04 (BP Energy Save Bypass Speed Increase)

Frequency Commanded to less than

E1-04 minus S4-02 (BP Energy Save

Bypass Trigger Level)

Speed

Search

Occurs

L2-03

Bypass Run

Figure 1.81 Energy Savings Mode

n

S4-01: BP Auto Transfer on Fault Enable

Enables Auto-Transfer when a fault occurs.

No.

Name

Setting Range

Default

S4-01

BP Auto Transfer on Fault Enable

0 or 1

0

Setting 0: No Transfer after Fault
Setting 1: Transfer to Bypass after Fault

n

S4-02: BP Energy Save Bypass Trigger Level

Delta used to determine when to switch into Energy Save Bypass. This allows for lower frequency output values to also trigger

Energy Save Bypass functionality. A transfer to bypass occurs after the drive reaches the programmed output frequency (E1-04

to S4-02) for the time specified in the BP Energy Save Bypass Timer (S4-03). Additionally, if frequency input is set below

E1-04 to S4-02, the drive exits Energy Save Bypass. Setting S4-02 to 0 disables Energy Save Bypass functionality.

1.11 S: Special Parameters

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

149