Setting

Specification

Characteristic

Application

8

50 Hz, Mid starting torque

High starting torque

Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m.
• A large amount of starting torque is required.
• An AC reactor is installed.

9

50 Hz, High starting torque

A

60 Hz, Mid starting torque

B

60 Hz, High starting torque

C

90 Hz (with 60 Hz base)

Constant output

Output voltage is constant when operating at greater than

60 Hz.

D

120 Hz (with 60 Hz base)

E

180 Hz (with 60 Hz base)

F

<1>

60 Hz

Variable torque

Used for variable torque applications. The default setting is

the same as V/f pattern Setting 7.

<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04

to E1-13 are equal to predefined V/f pattern 1.

The following tables show details on predefined V/f patterns.

Predefined V/f Patterns for Models 5A0003 to 5A0009

Table 1.16 Constant Torque Characteristics, Settings 0 to 3

Setting = 0

50 Hz

Setting = 1

60 Hz

Setting = 2

60 Hz

Setting = 3

72 Hz

0

25.9

575

1.3 2.5

50

43.1

V

oltage (V)

Frequency (Hz)

0

25.9

43.1

575

1.5 3

60

V

oltage (V)

Frequency (Hz)

0

25.9

43.1

575

1.5 3

60

50

V

oltage (V)

Frequency (Hz)

0

25.9

43.1

575

1.5 3

72

60

V

oltage (V)

Frequency (Hz)

Table 1.17 Derated Torque Characteristics, Settings 4 to 7

Setting = 4

50 Hz

Setting = 5

50 Hz

Setting = 6

60 Hz

Setting = 7

60 Hz

0

23.0

575

1.3

25

50

100.6

V

oltage (V)

Frequency (Hz)

0

25.9

575

1.3

25

50

143.8

V

oltage (V)

Frequency (Hz)

0

23.0

575

1.5

30

60

100.6

V

oltage (V)

Frequency (Hz)

0

25.9

575

1.5

30

60

143.8

V

oltage (V)

Frequency (Hz)

Table 1.18 High Starting Torque, Settings 8 to B

Setting = 8

50 Hz

Setting = 9

50 Hz

Setting = A

60 Hz

Setting = B

60 Hz

0

31.6

575

1.3 2.5

50

54.6

V

oltage (V)

Frequency (Hz)

0

37.4

575

1.3 2.5

50

69.0

V

oltage (V)

Frequency (Hz)

0

31.6

575

1.5 3

60

54.6

V

oltage (V)

Frequency (Hz)

0

43.1

575

1.5 3

60

69.0

V

oltage (V)

Frequency (Hz)

Table 1.19 Rated Output Operation, Settings C to F

Setting = C

90 Hz

Setting = D

120 Hz

Setting = E

180 Hz

Setting = F

60 Hz

0

25.9

43.1

575

1.5 3

90

60

V

oltage (V)

Frequency (Hz)

0

25.9

43.1

575

1.5 3

120

60

V

oltage (V)

Frequency (Hz)

0

25.9

43.1

575

1.5 3

180

60

V

oltage (V)

Frequency (Hz)

0

25.9

43.1

575

1.5 3

60

V

oltage (V)

Frequency (Hz)

1.5 E: Motor Parameters

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

63

1

Parameter Details