Setting 5: Feedback Loss Fault

If the PI feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FbL - Feedback Low” fault

will be displayed. If the PI feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FbH - Feedback

High” fault will be displayed. Both events trigger a fault output (H1-oo = E) and cause the drive to stop the motor. Detection

is disabled when PI is disabled by digital input (H1-oo = 19).

n

b5-13: PI Feedback Low Detection Level

Sets the feedback level used for PI feedback low detection. The PI feedback must fall below this level for longer than the time

set to b5-14 before feedback loss is detected.

No.

Name

Setting Range

Default

b5-13

PI Feedback Low Detection Level

0 to 100%

0%

n

b5-14: PI Feedback Low Detection Time

Sets the time that the PI feedback has to fall below b5-13 before feedback loss is detected.

No.

Name

Setting Range

Default

b5-14

PI Feedback Low Detection Time

0.0 to 25.5 s

1.0 s

n

b5-36: PI Feedback High Detection Level

Sets the feedback level used for PI feedback high detection. The PI feedback must exceed this level for longer than the time

set to b5-37 before feedback loss is detected.

No.

Name

Setting Range

Default

b5-36

PI Feedback High Detection Level

0 to 100%

100%

n

b5-37: PI Feedback High Detection Time

Sets the time that the PI feedback must exceed the value set to b5-36 before feedback loss is detected.

No.

Name

Setting Range

Default

b5-37

PI Feedback High Detection Time

0.0 to 25.5 s

1.0 s

n

PI Sleep/Snooze

The PI Sleep/Snooze function stops the drive when the PI output or the frequency reference falls below the PID Sleep/Snooze

operation level for a certain time. The drive will resume operating when the PI output or frequency reference rise above the

PI Sleep/Snooze operation level for the specified time. An example of PI Sleep/Snooze operation appears in the figure below.

PI Output

PI Sleep/Snooze
Level (b5-15)

Sleep Delay Time

Sleep Delay Time

Run command enabled

Continues to output “During Run”

Internal Run

command

External Run

command

During Run

Stop

b5-16

b5-16

Run

Figure 1.18 PI Sleep/Snooze Operation

Notes on Using the PI Sleep/Snooze Function

• The PI Sleep/Snooze function is active even when PI control is disabled.
• The PI Sleep/Snooze function stops the motor according to the stopping method set to b1-03.
The PI Snooze Function is a variation on the Sleep Function. Set b5-21 to 2 to select the PI Snooze function. After selecting

the Snooze Function, the drive monitors the output frequency. If the output frequency drops below the PI Snooze Level (b5-22),

and stays below that level for at least the time set to b5-23, PI Snooze Delay Time, the drive output shuts off.

1.2 b: Application

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

43

1

Parameter Details