beautypg.com

Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 290

background image

Setting 0: MEMOBUS/Modbus
Setting 1: N2
Setting 2: P1
Setting 3: BACnet

n

H5-09: Communications Fault Detection Time

Sets the time the communications must be lost before the drive triggers a CE fault.

No.

Name

Setting Range

Default

H5-09

Communications Fault Detection Time

0.0 to 10.0 s

2.0 s

n

H5-10: Unit Selection for MEMOBUS/Modbus Register 0025H

Note:

Leave parameter setting at default (Setting 0: 0.1 V units) for N2.

Sets the unit for the output voltage monitor value in MEMOBUS/Modbus register 0025H.

No.

Name

Setting Range

Default

H5-10

Unit Selection for MEMOBUS/Modbus Register 0025H

0 or 1

0

Setting 0: 0.1 V units
Setting 1: 1 V units

n

H5-11: Communications Enter Function Selection

Selects whether an Enter command is necessary to change parameter values via serial communications.

No.

Name

Setting Range

Default

H5-11

Communications Enter Function Selection

0 or 1

0

Setting 0: Enter command necessary

Parameter changes become effective after an Enter command. An Enter command must only be sent after the last parameter

change, not for each single parameter.

Setting 1: Enter command not necessary

Parameter value changes become effective immediately without the need to send an Enter command.

n

H5-12: Run Command Method Selection

Selects the type of sequence used when the Run command source is set to serial communications

(b1-02, b1-16 = 2).

No.

Name

Setting Range

Default

H5-12

Run Command Method Selection

0 or 1

0

Setting 0: FWD/Stop, REV/Stop

Setting B0 1 (bit 0 of MEMOBUS/Modbus register 0001H) will start and stop the drive in the forward direction. Setting B0

2 (bit 1 of MEMOBUS/Modbus register 0001H) will start and stop the drive in reverse.

Setting 1: Run/Stop, FWD/REV

Setting B0 1 (bit 0 of MEMOBUS/Modbus register 0001H) will start and stop the drive. Setting B0 2 (bit 1 of MEMOBUS/

Modbus register 0001H) changes the direction.

D.4 N2 Setup Parameters

290

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual