Metasys n2 binary output (bo) summary – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 298

background image

Object ID

Object Name

Default

Off (0) State

On (1) State

BI 10

Multi-Function Output 1 (H2-01)

0

Off

On

BI 11

Multi-Function Output 2 (H2-02)

0

Off

On

BI 12

Multi-Function Output 3 (H2-03)

0

Off

On

BI 13

Safety Interlock Monitor

0

Safety Clear Terminal 3 Closed

Safety Set Terminal 3 Open

BI 14

HAND/AUTO Reference Monitor

0

REMOTE

LOCAL

BI 15

Multi-Function Input S3 Monitor

0

Off

On

BI 16

Multi-Function Input S4 Monitor

0

Off

On

BI 17

Multi-Function Input S5 Monitor

0

Off

On

BI 18

Multi-Function Input S6 Monitor

0

Off

On

BI 19

Multi-Function Input S7 Monitor

0

Off

On

u

Metasys N2 Binary Output (BO) Summary

Table D.7 Metasys N2 Binary Output Summary (Z1000 to Metasys N2)

Object ID

Object Name

Default

Off (0) State

On (1) State

BO 1

Run Forward Command

0

Stop

Forward

BO 2

Run Reverse Command

0

Stop

Reverse

BO 3

Serial Fault (EF0) Command

0

No Fault

Fault

BO 4

Fault Reset Command

0

No Reset

Reset

BO 5

Multi-Function Input S3 (H1-03)

0

Off

On

BO 6

Multi-Function Input S4 (H1-04)

0

Off

On

BO 7

Multi-Function Input S5 (H1-05)

0

Off

On

BO 8

Multi-Function Input S6 (H1-06)

0

Off

On

BO 9

Multi-Function Input S7 (H1-07)

0

Off

On

BO10

Panel Lock

0

LOCAL/REMOTE and Stop/Reset Keys

Enabled

LOCAL/REMOTE and Stop/Reset Keys

Disabled

BO 11

Communication Fault Enable

0

EF0 Not Activated if Cable Loss Occurs

EF0 Activated if Cable Loss Occurs

D.7 Metasys N2 Point Database

298

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual