Sequence Timers 2 to 4

These timers operate identically to Sequence Timer 1. Parameters S2-06 to S2-20 configure Sequence Timers 2 to 4.

Priority

If multiple sequence timers overlap, the timer with the lowest number has priority.
Sequence Timer 1 = highest priority
Sequence Timer 4 = lowest priority

Examples of Sequence Timers

If multiple sequence timers overlap, the timer with the lowest number has priority.
Sequence Timer 1 = highest priority
Sequence Timer 4 = lowest priority

Mon

Tue

Wed

Thur

Fri

Sat

Sun

0:00
1:00
2:00
3:00
4:00
5:00
6:00

Sequence Timer 3

Run at d1-03

7:00
8:00
9:00

10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00

Sequence Timer 4

18:00
19:00

Activate Sequence

20:00

Timer 4 digital output

21:00
22:00
23:00

Sequence Timer 1

Run at d1-01

Sequence Timer 2

Run at d1-02 with PI control disabled

Figure 1.72 Sequence Timer Example 1

Mon

0:00

Sequence Timer 2

1:00

(cont.)

2:00
3:00
4:00
5:00
6:00

Sequence Timer 2

Run at d1-03

7:00
8:00
9:00

10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00

Sequence Timer 1

Run at d1-01

Sun

Sat

Fri

Thur

Wed

Tue

Figure 1.73 Sequence Timer Example 2