1.6 F: Option Settings

u

F6: Communication Option Card

Parameters F6-01 through F6-03 and F6-06 through F6-08 are used for EtherNet/IP and LONWORKS options.

n

F6-01: Communications Error Operation Selection

Determines drive operation when a communication error occurs.

No.

Parameter Name

Setting Range

Default

F6-01

Communications Error Operation Selection

0 to 4

1

Setting 0: Ramp to Stop (Use the Deceleration Time Set to C1-02)

Setting 1: Coast to Stop

Setting 2: Fast Stop (Use the Fast Stop Time Set to C1-09)

Setting 3: Alarm Only (Continue Operation)

n

F6-02: External Fault from Comm. Option Detection Selection

Determines the detection method of an external fault initiated by a communication option (EF0).

No.

Parameter Name

Setting Range

Default

F6-02

External Fault from Comm. Option Detection Selection

0, 1

0

Setting 0: Always Detected

Setting 1: Detection during Run Only

n

F6-03: External Fault from Comm. Option Operation Selection

Determines drive operation when an external fault is initiated by a communication option (EF0).

No.

Parameter Name

Setting Range

Default

F6-03

External Fault from Comm. Option Operation Selection

0 to 3

1

Setting 0: Ramp to Stop

Setting 1: Coast to Stop

Setting 2: Fast Stop

Setting 3: Alarm Only (Continue Operation)

n

F6-06: Torque Reference/Torque Limit Selection from Comm. Option

Selects whether torque reference and torque limit values are assigned to the drive from the network.

No.

Parameter Name

Setting Range

Default

F6-06

Torque Reference/Torque Limit Selection from Comm. Option

0, 1

0

Setting 0: Disabled

Setting 1: Enabled

n

F6-07: NetRef/ComRef Function Selection

Selects the treatment of multi-step speed inputs when the NetRef command is set.

No.

Parameter Name

Setting Range

Default

F6-07

NetRef/ComRef Function Selection

0, 1

0

1.6 F: Option Settings

70

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual