Figure 1.29 V/f Pattern

Note:

1. The following condition must be true when setting up the V/f pattern: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
2. To make the V/f pattern a straight line below E1-06, set E1-09 equal to E1-07. In this case the E1-08 setting is disregarded.
3. E1-03 is unaffected when the drive is initialized, but E1-04 through E1-13 return to their default values.
4. Only use E1-11, E1-12, and E1-13 to fine-tune the V/f pattern in the constant output range. These parameters rarely need to be changed.

u

E2: Motor 1 Parameters

These parameters contain the motor data needed for motor 1. Enter the motor data into these parameters when Auto-Tuning

cannot be performed.

Note:

The function for switching between two motors cannot be used with a PM motor. E2-oo parameters are hidden when OLV/PM control

mode is selected (A1-02 = 5).

n

E2-01: Motor Rated Current

Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on

the motor nameplate.

No.

Parameter Name

Setting Range

Default

E2-01

Motor Rated Current

10% to 200% of the drive

rated current

Determined by

o2-04

Note:

1. Display is in the following units: 5A0007 to 5A0017: 0.01 A units; 5A0022 to 5A0242: 0.1 A units.
2. An oPE02 error will occur if the motor rated current in E2-01 is set lower than the motor no-load current in E2-03. Set E2-03 correctly

to prevent this error.

n

E2-02: Motor Rated Slip

Sets the motor rated slip in Hz to provide motor control, protect the motor, and calculate torque limits.

No.

Parameter Name

Setting Range

Default

E2-02

Motor Rated Slip

0.00 to 20.00 Hz

Determined by

o2-04

If Auto-Tuning cannot be performed, calculate the motor rated slip using the information written on the motor nameplate and

the formula below:
E2-02 = f - (n × p)/120
(f: rated frequency (Hz), n: rated motor speed (r/min), p: number of motor poles)

n

E2-03: Motor No-Load Current

Set the no-load current for the motor in amperes when operating at the rated frequency and the no-load voltage. The drive sets

E2-03 during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2). The motor no-load current

listed in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer to receive a copy of the

motor test report.

No.

Parameter Name

Setting Range

Default

E2-03

Motor No-Load Current

0 to [E2-01]

Determined by

o2-04

Note:

Display is in the following units: 5A0007 to 5A0017: 0.01 A units; 5A0022 to 5A0242: 0.1 A units.

1.5 E: Motor Parameters

66

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual