D4-01: frequency reference hold function selection – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 59

background image

Frequency

Reference

Output
Frequency

Jump

Frequency

Width (d3-04)

Jump

Frequency 3

d3-03

Jump

Frequency 2

d3-02

Jump

Frequency 1

d3-01

Frequency

reference

decreases

Frequency

reference
increases

Jump

Frequency

Width (d3-04)

Jump

Frequency

Width (d3-04)

Figure 1.26 Jump Frequency Operation

Note:

1. The drive will use the active accel/decel time to pass through the specified dead band range, but will not allow continuous operation in

that range.

2. When setting more than one Jump frequency, make sure that d3-01≥ d3-02 ≥ d3-03.

u

d4: Frequency Reference Hold and Up/Down 2 Function

n

d4-01: Frequency Reference Hold Function Selection

This parameter is effective when either of the digital input functions listed below are used:
• Accel/decel ramp hold function (H1-oo= A)
• Up/Down function (H1-oo = 10 and 11)

No.

Parameter Name

Setting Range

Default

d4-01

Frequency Reference Hold Function Selection

0, 1

0

The operation depends on the function used with parameter d4-01.

Setting 0: Disabled

• Acceleration hold

The hold value will be reset to 0 Hz when the Stop command is entered or the drive power is switched off. The active

frequency reference will be the value the drive uses when it restarts.

• Up/Down

The frequency reference value will be reset to 0 Hz when the Stop command is entered or the drive power is switched off.

The drive will start from 0 Hz when it is restarted.

Setting 1: Enabled

• Acceleration hold

The last hold value will be saved when the Run command or the drive power is switched off and the drive will use the saved

value as the frequency reference when it restarts. Make sure to continuously enable the multi-function input terminal set for

“Accel/decel ramp hold” (H1-oo = A) or the hold value will be cleared when the power is switched on.

1.4 d: Reference Settings

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

59

1

Parameter Details