beautypg.com

Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 206

background image

H1 Multi-Function Digital Input Selections

H1-oo

Setting

Function

LCD Display

Description

Page

40

Forward run command

(2-Wire sequence)

FwdRun 2Wire Seq

Open: Stop

Closed: Forward run

Note:

Cannot be set together with settings 42 or 43.

78

41

Reverse run command

(2-Wire sequence)

RevRun 2WireSeq

Open: Stop

Closed: Reverse run

Note:

Cannot be set together with settings 42 or 43.

78

42

Run command

(2-Wire sequence 2)

Run/Stp 2WireSeq

Open: Stop

Closed: Run

Note:

Cannot be set together with settings 40 or 41.

78

43

FWD/REV command

(2-Wire sequence 2)

FWD/REV 2WireSeq

Open: Forward

Closed: Reverse

Note:

Determines motor direction, but does not issue a Run command.

Cannot be set together with settings 40 or 41.

78

44

Offset frequency 1

Offset Freq 1

Closed: Adds d7-01 to the frequency reference.

79

45

Offset frequency 2

Offset Freq 2

Closed: Adds d7-02 to the frequency reference.

79

46

Offset frequency 3

Offset Freq 3

Closed: Adds d7-03 to the frequency reference.

79

50

Motor Pre-Heat 2

Motor Preheat 2

Closed: Triggers Motor Pre-Heat 2.

79

51

Sequence Timer Disable SeqTimer Disable

Closed: Drive ignores sequence timers and runs normally.

79

52

Sequence Timer Cancel SeqTimer Cancel

Closed: Sequence Timer Cancel .

79

60

Motor pre-heat 1

DCInj Activate

Closed: Triggers Motor pre-heat 1.

79

61

External Speed Search

command 1

Speed Search 1

Closed: Activates Current Detection Speed Search from the maximum output

frequency (E1-04).

79

62

External Speed Search

command 2

Speed Search 2

Closed: Activates Current Detection Speed Search from the frequency reference.

79

63

Field weakening

Field Weak

Closed: The drive performs Field Weakening control as set for d6-01 and d6-02.

79

65

KEB Ride-Thru 1 (N.C.) KEB Ridethru NC

Open: KEB Ride-Thru 1 enabled.

80

66

KEB Ride-Thru 1 (N.O.) KEB Ridethru NO

Closed: KEB Ride-Thru 1 enabled.

80

67

Communications test

mode

Comm Test Mode

Tests the MEMOBUS/Modbus RS-422/RS-485 interface. Displays “PASS” if the

test completes successfully.

80

68

High slip braking

HighSlipBraking

Closed: Activates High Slip Braking to stop the drive during a Run command.

80

69

Jog 2

Jog 2

Cause the drive to ramp to the jog frequency (d1-17).

80

6A

Drive enable

Drive Enable

Open: Drive disabled. If this input is opened during run, the drive will stop as

specified by b1-03.

Closed: Ready for operation.

80

6D

AUTO mode select

AUTO Mode Sel

Legacy Operation Mode (S5-04 = 0)
• Open: HAND reference is selected (based on S5-01)
• Closed: AUTO reference is selected (based on b1-01)
Normal Operation Mode (S5-04

≠ 0)

Note:

The drive will always be in AUTO mode at power up when

S5-04 is set to 1.

• Open: Drive is in OFF or HAND mode.
• Closed: Drive is in AUTO mode (when HAND mode select input is open)

80

6E

HAND mode select

HAND Mode Se

Legacy Operation Mode (S5-04 = 0)
• Open: AUTO reference is selected (based on b1-01)
• Closed: HAND reference is selected (based on S5-01)
Normal Operation Mode (S5-04

≠ 0)

Note:

The drive will always be in AUTO mode at power up when

S5-04 is set to 1.

• Open: Drive is in OFF or AUTO mode.
• Closed: Drive is in HAND mode. (when AUTO mode select input is open)

80

A.9 H Parameters: Multi-Function Terminals

206

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual