E2-04: Number of Motor Poles

Set the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will automatically

be saved to E2-04.

No.

Parameter Name

Setting Range

Default

E2-04

Number of Motor Poles

2 to 48

4

n

E2-05:Motor Line-to-Line Resistance

Sets the line-to-line resistance of the motor stator winding. If Auto-Tuning completes successfully, this value is automatically

calculated. Enter this value as line-to-line and not for each motor phase.
If Auto-Tuning is not possible, contact the motor manufacturer to find out the line-to-line resistance or measure it manually.

When using the manufacturer motor test report, calculate E2-05 by one of the formulas below:
• E-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.
• B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.
• F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the test report at 115 °C.

No.

Parameter Name

Setting Range

Default

E2-05

Motor Line-to-Line Resistance

0.000 to 65.000 Ω

Determined by

o2-04

n

E2-10: Motor Iron Loss for Torque Compensation

Sets the motor iron loss in watts.

No.

Parameter Name

Setting Range

Default

E2-10

Motor Iron Loss for Torque Compensation

0 to 65535 W

Determined by

o2-04

n

E2-11: Motor Rated Power

Sets the motor rated power in kW. If Auto-Tuning completes successfully, the value entered to T1-02 will automatically be

saved to E2-11.

No.

Parameter Name

Setting Range

Default

E2-11

Motor Rated Power

0.00 to 650.00 kW

Determined by

o2-04

n

Setting Motor Parameters Manually

Follow the instructions below when setting motor-related parameters manually instead of Auto-Tuning. Refer to the motor

test report included with the motor to ensure the correct data is entered into the drive.

Set the Motor Rated Current

Enter the motor rated current listed on the nameplate of the motor to E2-01.

Set the Motor Rated Slip

Calculate the motor rated slip using the base speed listed on the motor nameplate. Refer to the formula below, then enter that

value to E2-02.
Motor rated slip = rated frequency [Hz] – base speed [r/min] × (no. of motor poles) / 120

Set the No-Load Current

Enter the no-load current at rated frequency and rated voltage to E2-03. This information is not usually listed on the nameplate.

Contact the motor manufacturer if the data cannot be found.
The default setting of the no-load current is for performance with a 4-pole Yaskawa motor.

Set the Line-to-Line Resistance

E2-05 is normally set during Auto-Tuning. If Auto-Tuning cannot be performed, contact the motor manufacturer to determine

the correct resistance between motor lines. The motor test report can also be used to calculate this value using the formulas

below:
• E-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.

1.5 E: Motor Parameters

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

67

1

Parameter Details