Table 1.14 Multi-Step Speed Reference and Terminal Switch Combinations

Reference

Multi-Step Speed

H1-oo = 3

Multi-Step Speed 2

H1-oo = 4

Jog Reference

H1-oo = 6

Frequency Reference 1 (set in b1-01)

OFF

OFF

OFF

Frequency Reference 2

(d1-02 or input terminal A1, A2)

ON

OFF

OFF

Frequency Reference 3

(d1-03 or input terminal A1, A2)

OFF

ON

OFF

Frequency Reference 4 (d1-04)

ON

ON

OFF

Jog Frequency Reference (d1-17)

<1>

ON

<1> The Jog frequency overrides all other frequency references.

d1-04

d1-17

ON

ON

ON

ON

ON

Multi-step Speed Ref. 2

Jog Reference

Time

Multi-step Speed Ref. 1

Frequency

reference

d1-01

(A1)

d1-02

(A2)

d1-03

FWD (REV) Run/Stop

Figure 1.24 Preset Reference Timing Diagram

u

d2: Frequency Upper/Lower Limits

Upper and lower frequency limits prevent motor speed from going above or below levels that may cause resonance or

equipment damage.

n

d2-01: Frequency Reference Upper Limit

Sets the maximum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency

references.
Even if the frequency reference is set to a higher value, the drive internal frequency reference will not exceed this value.

No.

Parameter Name

Setting Range

Default

d2-01

Frequency Reference Upper Limit

0.0 to 110.0%

100.0%

n

d2-02: Frequency Reference Lower Limit

Sets the minimum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency

references.
If a lower reference than this value is entered, the drive will run at the limit set to d2-02. If the drive is started with a lower

reference than d2-02, it will accelerate up to d2-02.

No.

Parameter Name

Setting Range

Default

d2-02

Frequency Reference Lower Limit

0.0 to 110.0%

0.0%

1.4 d: Reference Settings

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

57

1

Parameter Details