S6: Phase Order Selections

n

S6-01: Emergency Override Speed

Sets the speed command used in emergency override mode when S6-02 = 0.

No.

Name

Setting Range

Default

S6-01

Emergency Override Speed

0.00 to 240.00 Hz

0.00 Hz

n

S6-02: Emergency Override Reference Selection

Selects the frequency reference source for the Emergency Override function (H1-oo= AF or B0). Emergency Override

ignores faults such as oL2, oH1, oL1/oL2/oL3, EFoo, oH1/oH3/oH4, LL3, rH, oPr, CPF, PI faults, LF/LF2, UL3, PF, and

any other faults, if possible.

No.

Name

Setting Range

Default

S6-02

Emergency Override Reference Selection

0, 1

0

Setting 0: Use S6-01 Reference
Setting 1: Use AUTO Reference

n

S6-03: ov2 Detect Time

Sets the detection time of ov2 in 0.1 s increments.

No.

Name

Setting Range

Default

S6-03

ov2 Detect Time

0.0 to 1200.0 s

10.0 s

n

S6-07: Output Phase Loss Detection Level for Dynamic Audible Noise Control

Sets the output phase loss detection level for Dynamic Audible Noise Control. Decrease the setting in steps of 10% when

output phase loss is detected erroneously. This setting rarely needs to be changed.

No.

Name

Setting Range

Default

S6-07

Output Phase Loss Detection Level for Dynamic Audible Noise

Control

10.0 to 100.0%

100.0%

1.11 S: Special Parameters

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

153