S4: bypass operation, S5: hoa keypad parameters – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 228

background image

u

S4: Bypass Operation

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

S4-01

(322B) BP Auto Transfer on

Fault Enable

BP Fault Trnsfer

0: Disabled

1: Enabled

0: No transfer after fault

1: Transfer to bypass after fault

Default: 1

Range: 0, 1

149

S4-02

(322C) Secondary PI User

Display

BP Enrgy Sav Lvl

Delta used to determine when to switch into Energy Save Bypass.

This allows for lower frequency output values to also trigger

Energy Save Bypass functionality.

Default: 0 Hz

Min.: 0

Max.: 20

149

S4-03

(322D) BP Energy Save Bypass

Timer

BP Enrgy Sav TMR

Sets the time in seconds that the drive should run at the specified

speed before entering Energy Save Bypass mode.

Default: 60 s

Min.: 10

Max.: 60000

150

S4-04

(322E) BP Energy Save Bypass

Speed Increase

BP Enrgy Sav Inc

Sets the value in Hz that the drive will increase the output

frequency above E1-04 before performing an Energy Save

transfer to bypass.

Default: 6 Hz

Min.: 0

Max.: 10

150

u

S5: HOA Keypad Parameters

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

S5-01

(322F)

HAND Frequency

Reference Selection

HAND Fref Source

0: Operator

1: Terminals

2: d1-16

3: S5-05

4: Set by b1-01

0: HOA keypad

1: Terminals

2: d1-16

3: S5-05

4: Determined by b1-01

Default: 0

Range: 0 to 4

150

S5-02

(3230)

HAND/AUTO During

Run Selection

HAND/AUTO

@Run

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

150

S5-03

(3231)

HAND Mode PI

Selection

HAND Mode PI Sel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

150

S5-04

(3232)

HAND Mode Behavior

Selection

HAND BehaviorSel

0: Legacy

1: Normal

2: Normal w/

Memory

0: Legacy operation mode

1: Normal operation mode

2: Normal with memory

Note:

The drive will always be in AUTO mode at power

up with S5-04 = 1.

Default: 1

Range: 0 to 2

150

S5-05

(3233)

HAND Frequency

Reference 1

HAND Freq Ref 2

Sets the frequency reference used in HAND mode when S5-01 is

set to 2.

Default: 0.00

Hz

Min.: 0.00

Max.: 240.00

152

S5-07

(3235)

HAND Key Function

Selection (HOA

Keypad)

Oper HAND Key

0: Disabled

1: Enabled

Determines whether the HAND key on the HOA keypad will be

enabled for switching between HAND and AUTO.

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

152

A.13 S: Special Application

228

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual