1.12 T: Motor Tuning

Auto-Tuning automatically sets and tunes parameters required for optimal motor performance.

u

T1: Parameter Settings during Induction Motor Auto-Tuning

The T1-oo parameters set the Auto-Tuning input data for induction motor tuning.

Note:

For motors operating in the field weakening range, first perform the Auto-Tuning with the base data. After Auto-Tuning is complete, change

E1-04, Maximum Output Frequency, to the desired value.

n

T1-01: Auto-Tuning Mode Selection

Sets the type of Auto-Tuning to be used. Refer to the User Manual packaged with the drive for details on the different types

of Auto-Tuning.

No.

Name

Setting Range

Default

T1-01

Auto-Tuning Mode Selection

2, 3 (V/f)

2 (V/f)

Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance
Setting 3: Rotational Auto-Tuning for V/f Control Energy Saving

n

T1-02: Motor Rated Power

Sets the motor rated power according to the motor nameplate value.

Note:

Use the following formula to convert HP to kW: kW = HP x 0.746.

No.

Name

Setting Range

Default

T1-02

Motor Rated Power

0.00 to 650.00 kW

Determined by o2-04

n

T1-03: Motor Rated Voltage

Sets the motor rated voltage according to the motor nameplate value. Enter the voltage base speed when the motor operates

above base speed. Enter the voltage needed to operate the motor under no-load conditions at rated speed to T1-03.

No.

Name

Setting Range

Default

T1-03

Motor Rated Voltage

0.0 to 733.1 V

575.0 V

n

T1-04: Motor Rated Current

Sets the motor rated current according to the motor nameplate value. Enter the current at the motor base speed.

No.

Name

Setting Range

Default

T1-04

Motor Rated Current

10.0 to 300.0% of drive rated

current

Determined by

o2-04

n

T1-05: Motor Base Frequency

Sets the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used or

the motor is used in the field weakening area, enter the maximum frequency to E1-04 after Auto-Tuning is complete.

No.

Name

Setting Range

Default

T1-05

Motor Base Frequency

0.0 to 240.0 Hz

60.0 Hz

n

T1-06: Number of Motor Poles

Sets the number of motor poles according to the motor nameplate value.

No.

Name

Setting Range

Default

T1-06

Number of Motor Poles

2 to 48

4

1.12 T: Motor Tuning

154

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual