beautypg.com

Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 48

background image

Setting 2: Quadratic

The monitor displays 1/(PI output)

2

Setting 3: Cubic

The monitor displays 1/(PI output)

3

n

b5-43/b5-44: Custom PI Output Monitor Setting 1/2

Set the maximum monitor value at maximum frequency. U5-14 and U5-15 show Custom PI output. U5-14 shows the upper

4 digits and U5-15 shows the lower 4 digits. It shows 999999.99 maximum.

No.

Name

Setting Range

Default

b5-43

Custom PI Output Monitor Setting 2

0 to 9999

0

b5-44

Custom PI Output Monitor Setting 2

0.00 to 99.99

0.00

n

b5-45: Custom PI Output Monitor Setting 3

b5-14 shows Custom PI Output. b5-45 sets the minimum display value at zero speed. This function is effective when b5-42

is set to 0 (Linear).

No.

Name

Setting Range

Default

b5-45

Custom PI Output Monitor Setting 3

0

999.9

n

b5-46: PI Setpoint Monitor Unit Selection

Sets the HOA keypad display units in U5-01 and U5-04 when b5-20 is set to 3.

No.

Name

Setting Range

Default

b5-46

PI Setpoint Monitor Unit Selection

0 to 14

0

Setting 0: WC (Inch of Water)
Setting 1: PSI (Pounds per Square Inch)
Setting 2: GPM (Gallons per Minute)
Setting 3: F (Degrees Fahrenheit)
Setting 4: CFM (Cubic Feet per Minute)
Setting 5: CMH (Cubic Meters per Hour)
Setting 6: LPH (Liters per Hour)
Setting 7: LPS (Liters per Second)
Setting 8: Bar (Bar)
Setting 9: Pa (Pascal)
Setting 10: C (Degrees Celsius)
Setting 11: Mtr (Meters)
Setting 12: Ft (Feet)
Setting 13: LPM (Liters per Minute)
Setting 14: CMM (Cubic Meters per Minute)

n

b5-47: Reverse Operation Selection 2 by PI Output

Determines whether a negative PI output reverses the direction of drive operation. When the PI function is used to trim the

frequency reference (b5-01 = 3), this parameter has no effect and the PI output will not be limited

(same as b5-11 = 1).

No.

Name

Setting Range

Default

b5-47

Reverse Operation Selection 2 by PI Output

0, 1

1

Setting 0: Reverse Disabled

Negative PI output will be limited to zero and the drive output will be stopped.

1.2 b: Application

48

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual