1.4 d: Reference Settings

The figure below gives an overview of the reference input, selections, and priorities.

=4

=0

=1

=2

=3

b1-01

(Freq.Reference Source1)

S5-05

d1-16

Terminal A1/A2

b1-01

(Freq.Reference Source1)

S5-01

(HAND Fref Source)

Terminal A1/A2

MEMOBUS/Modbus

Comm.

Option Card

d1-01

(Freq.Ref.1)

=3

=2

=1

=0

b1-01

(Freq.Reference Source1)

d1-17

d1-17

HOA Keypad (d1-01)

HOA Keypad (d1-04)

HOA Keypad (d1-03)

HOA Keypad (d1-02)

Terminal A1/A2

MEMOBUS/Modbus Comm.

Option Card

=0

=1

=2

=6

Frequency Reference

Terminal A1/A2

MEMOBUS/Modbus

Comm.

Option Card

d1-01

(Freq.Ref.1)

=3

=2

=1

=0

AUTO,OFF

HAND

d2-03

(Freq.Ref.Lower Limit)

Multi-Step Speed

Set by b1-01

0

0

1 1

NetRef

ComRef

d2-03

(Freq.Ref.Lower Limit)

Multi-Step Speed

S5-01<4

& HAND

JOG

EmergencyOverride
: OFF

=3

=4

=5

Sequence Timer Operation Enable

OFF when using
Option Card

Figure 1.23 Frequency Reference Setting Hierarchy

u

d1: Frequency Reference

n

d1-01 to d1-04, d1-16, and d1-17: Frequency References 1 to 4, 16, and Jog Frequency

Reference

The drive lets the user switch between up to 5 preset frequency references during run (including the Jog reference) through

the digital input terminals. The drive uses the acceleration and deceleration times that have been selected when switching

between each frequency reference.
The Jog frequency overrides all other frequency references and must be selected by a separate digital input.
The multi-speed references 1 and 2 can be provided by analog inputs.

No.

Parameter Name

Setting Range

Default

d1-01 to d1-04

Frequency Reference 1 to 4

0.00 to 240.00 Hz

<1>

<2>

0.00 Hz

<2>

d1-16

Frequency Reference 16

0.00 to 240.00 Hz

<1>

<2>

0.00 Hz

<2>

d1-17

Jog Frequency Reference

0.00 to 240.00 Hz

<1>

<2>

6.00 Hz

<2>

<1> The upper limit is determined by the maximum output frequency (E1-04) and upper limit for the frequency reference (d2-01).
<2> Setting units are determined by parameter o1-03. The default is “Hz” (o1-03 = 0).

Multi-Step Speed Selection

To use several speed references for a multi-step speed sequence, set the H1-oo parameters to 3 and 4. To assign the Jog

reference to a digital input, set H1-oo to 6.
Notes on using analog inputs as Multi-Speed 1 and 2:
• The first frequency reference (Multi-Speed 1) comes from the source specified in b1-01. When using an analog input terminal

to supply the frequency reference, assign the frequency reference source to the control terminals (b1-01 = 1).

• When an analog input is set to “Auxiliary frequency 1” (H3-02 or H2-06 = 2), the value set to this input will be used as the

Multi-Step Speed 2 instead of the value set to parameter d1-02. If no analog inputs are set for “Auxiliary frequency 1”, then

d1-02 becomes the reference for Multi-Step Speed 2.

Select the different speed references as shown in

Table 1.14

.

Figure 1.24

illustrates the multi-step speed selection.

1.4 d: Reference Settings

56

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual