b5-26: PI Maximum Boost Time

Associated with the Snooze Function. In cases where the temporary PI Setpoint (intended PI setpoint + PI Setpoint Boost)

cannot be reached within the PI Maximum Boost Time (b5-26), the Setpoint Boost is interrupted and the Drive output is turned

off.

No.

Parameter Name

Setting Range

Default

b5-26

PI Maximum Boost Time

0 to 2600 s

0 s

n

b5-27: PI Snooze Feedback Level

The second method of initiating the Snooze Function. The drive output shuts off when the PI feedback level exceeds the PI

Snooze Feedback Level (b5-27).
Normal drive and PI operation return after the PI feedback drops below the PI Snooze Deactivation Level (b5-24). Snooze

activates when both b5-22 and b5-27 conditions are met. There is no time delay for deactivation.
Sets as a percentage of maximum frequency.

No.

Parameter Name

Setting Range

Default

b5-27

PI Snooze Feedback Level

0 to 100%

60%

n

b5-28: PI Feedback Function Selection

When b5-28 is set to 1, the square root of the PI feedback is compared to the PI Setpoint to determine appropriate drive output

to properly regulate the system.
This is helpful in cases where the measured feedback is pressure, but the PI loop needs to regulate flow.

No.

Parameter Name

Setting Range

Default

b5-28

PI Feedback Function Selection

0, 1

0

0: Disabled
1: Square Root

n

b5-29: PI Square Root Gain

A multiplier applied to the square root of the feedback. If the PI Function is regulating the flow of a closed loop system by

using a pressure feedback, it may be convenient to view the square root of the PI output using monitor U1-37.

No.

Parameter Name

Setting Range

Default

b5-29

PI Square Root Gain

0.00 to 2.00

0.00

n

b5-30: PI Feedback Offset

Sets PI feedback Offset as a percentage of maximum frequency.

No.

Parameter Name

Setting Range

Default

b5-30

PI Feedback Offset

0.00 to 100.00%

0.00%

n

b5-34: PI Output Lower Limit

Sets the minimum possible PI controller output as a percentage of the maximum output frequency (E1-04). The lower limit is

disabled when set to 0.00%

No.

Name

Setting Range

Default

b5-34

PI Output Lower Limit

-100.0 to 100.0%

0.0%

n

b5-35: PI Input Limit

Sets the maximum allowed PI input as a percentage of the maximum output frequency (E1-04). Parameter b5-35 acts as a

bipolar limit.

No.

Name

Setting Range

Default

b5-35

PI Input Limit

0 to 1000.0%

1000.0%

1.2 b: Application

46

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual