u

Wiring Diagram for Multiple Connections

Figure B.3

and

Figure E.4

explain the wiring diagrams for multiple connections using APOGEE FLN communication.

n

RS-485 Interface

Drive

Drive

Drive

S2

S2

S2

S–
S+
R–
R+
IG

S–
S+
R–
R+
IG

S–
S+
R–
R+
IG

R–
R+
S–
S+
IG

PLC

OFF

OFF

ON

Figure C.2 RS-485 Interface

Note:

1. Set DIP switch S2 to the ON position on the drive located at the end of the network. Set DIP switch S2 to the OFF positions on all other

slave devices.

2. Set H5-07 to 1 when using the RS-485 interface.

u

Network Termination

Terminate each APOGEE FLN network segment on both ends to eliminate signal reflections. Yaskawa recommends using

the Siemens Building Automation BLN Trunk Terminator (PN: 538-664) and setting the network termination switch on the

drive, S1-1, to OFF.

C.3 Connecting to a Network

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

271

C

APOGEE FLN (P1) Communications