Electrical Installation 2 - 22

DIP Switch S1 and Jumper CN15

Fig 2.10 DIP Switch S1 and Jumper CN15 Location

Dip Switch S1

DIP Switch S1 is described in this section. The functions of DIP switch S1 are shown in Table 2.13.

Fig 2.11 DIP Switch S1 Function

Jumper CN15

Jumper CN15 is described in this section. The jumper position of CH1 and CH2 determines the signal level of the
multi-function analog output FM and AM, respectively. The functions and positions of CN15 are shown in Table 2.14.

Table 2.13 DIP Switch S1

Name

Function

Setting

S1-1

RS-485 and RS-422 terminating resistance

OFF: No terminating resistance
ON: Terminating resistance of 110

Ω

Factory Default = OFF

S1-2

Input method for analog input A2

OFF: 0 to 10Vdc or -10 to 10Vdc (internal resistance: 20K

Ω)

ON: 4-20mA (internal resistance: 250

Ω)

Factory Default = ON

Table 2.14 Jumper CN15 Configuration Options

Jumper CN15 Configuration

Analog Output Monitor Configuration

Voltage Output (0-10Vdc) for terminals FM-AC (CH1) and AM-AC (CH2)

Current Output (4-20mA) for terminals FM-AC (CH1) and AM-AC (CH2)

Voltage Output (0-10Vdc) for terminals FM-AC (CH1)

Current Output (4-20mA) for terminals AM-AC (CH2)

Current Output (4-20mA) for terminals FM-AC (CH1)

Voltage Output (0-10Vdc) for terminals AM-AC (CH2)

S1

S1

ON/OFF
position

DIP Switch S1 located on
terminal board.

2

1

CH1

CH2

CH1

CH2

CH1

CH2

CH1

CH2

CN15