Specifications C - 3

480Vac

Table C.2 480Vac Drive Specifications

Model Number CIMR-F7U

40P4

40P7

41P5

42P2

43P7

44P0

45P5

47P5

4011

4015

4018

4022

Rated output

capacity

(kVA)

1.4

1.6

2.8

4.0

5.8

6.6

9.5

13.0

18.0

24.0

30.0

34.0

Horsepower

*2

0.5/0.75

1

2

3

5

-

7.5

10

15

20

25

30

Rated output current

(A)

1.8

2.1

3.7

5.3

7.6

8.7

12.5

17.0

24.0

31.0

39.0

45.0

Overload capacity

*3

(% of rated output
current for 60 sec)

150

Current limit (% of
rated output current)

150

Carrier frequency

*4

2kHz

Maximum output
frequency

300.0Hz

Rated output
capacity (kVA)

1.4

1.6

2.8

4.0

5.8

6.6

9.5

13.0

21.0

26.0

30.0

38.0

Horsepower

*2

0.5/0.75

1

2

3

5

-

7.5

10

15/20

25

30

-

Rated output current

(A)

1.8

2.1

3.7

5.3

7.6

8.7

12.5

17.0

27.0

34.0

40.0

50.4

Overload capacity

*3

(% of rated output
current for 60 sec)

120

120

120

120

120

120

120

120

107

109

117

107

Current limit

(

% of rated

output current)

120

Carrier frequency (kHz)

*5

15

15

15

15

15

15

15

15

8

10

10

10

Maximum output
frequency

400.0Hz

Maximum output voltage

3-phase; 380, 400, 415, 440, 460, or 480Vac (Proportional to input voltage.)

Rated voltage
Rated frequency

3-phase, 380, 400, 415, 440, 460 or 480Vac, 50/60Hz

Rated input current -

Heavy Duty

*1

(A)

2.2

2.5

4.4

6.4

9.0

10.4

15

20

29

37

47

50

Rated input current -

Normal Duty

*1

(A)

2.2

2.5

4.4

6.4

9.0

10.4

15

20

33

40

48

55

Allowable voltage
fluctuation

+ 10%, - 15%

Allowable frequency
fluctuation

±5%

Measures
for power
supply
harmonics

DC Reactor

Optional

12-pulse
Rectification

Not possible

*1 The difference between Heavy Duty ratings and the Normal Duty ratings for the Drive are the rated input and output current, overload capacity, carrier frequency, current limit,

and maximum output frequency. Parameter C6-01 must be set to value of “0” for Heavy Duty ratings and “2” for Normal Duty ratings. Factory default is Heavy Duty (C6-01=0).

*2 Horsepower ratings are based on 230V or 460V NEC Table 430.150. The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual

motor and Drive, be sure that the Drive's rated output current is appropriate for the motor's rated current.

*3 Model 2110 has an overload rating of 138% of rated output current for 60 seconds and a current limit rating of 138%. Models 4220 and 4300 have an overload rating of 150%

of rated output current for 45 seconds and a current limit rating of 150%.

*4 When setting the carrier frequency above the factory default, the Drive must be derated.
*5 Heavy Duty ratings for models 2110, 4220 and 4300 are effective in software version VSF103021 and higher.
*6 Each value shown is the Maximum carrier frequency and default carrier frequency.
*7 The carrier frequency for Heavy Duty is default to 2 kHz. Software version VSF103021 and higher may allow the carrier frequency to be increased above 2 kHz with a

reduction in continuous rated output current. Refer to C6-02 in Chapter 5 for further details.

O

utpu

t rat

ing

s

Heavy Du

ty

*1

No

rm

al Du

ty

*1

Power s

u

pp

ly c

h

ar

act

er

ist

ics

Cont

rol char

act

eri

sti

cs