480vac, Specifications c - 3 – Yaskawa F7 Drive User Manual User Manual
Page 216

Specifications C - 3
480Vac
Table C.2 480Vac Drive Specifications
Model Number CIMR-F7U
40P4
40P7
41P5
42P2
43P7
44P0
45P5
47P5
4011
4015
4018
4022
Rated output
capacity
(kVA)
1.4
1.6
2.8
4.0
5.8
6.6
9.5
13.0
18.0
24.0
30.0
34.0
Horsepower
*2
0.5/0.75
1
2
3
5
-
7.5
10
15
20
25
30
Rated output current
(A)
1.8
2.1
3.7
5.3
7.6
8.7
12.5
17.0
24.0
31.0
39.0
45.0
Overload capacity
*3
(% of rated output
current for 60 sec)
150
Current limit (% of
rated output current)
150
Carrier frequency
*4
2kHz
Maximum output
frequency
300.0Hz
Rated output
capacity (kVA)
1.4
1.6
2.8
4.0
5.8
6.6
9.5
13.0
21.0
26.0
30.0
38.0
Horsepower
*2
0.5/0.75
1
2
3
5
-
7.5
10
15/20
25
30
-
Rated output current
(A)
1.8
2.1
3.7
5.3
7.6
8.7
12.5
17.0
27.0
34.0
40.0
50.4
Overload capacity
*3
(% of rated output
current for 60 sec)
120
120
120
120
120
120
120
120
107
109
117
107
Current limit
(
% of rated
output current)
120
Carrier frequency (kHz)
*5
15
15
15
15
15
15
15
15
8
10
10
10
Maximum output
frequency
400.0Hz
Maximum output voltage
3-phase; 380, 400, 415, 440, 460, or 480Vac (Proportional to input voltage.)
Rated voltage
Rated frequency
3-phase, 380, 400, 415, 440, 460 or 480Vac, 50/60Hz
Rated input current -
Heavy Duty
*1
(A)
2.2
2.5
4.4
6.4
9.0
10.4
15
20
29
37
47
50
Rated input current -
Normal Duty
*1
(A)
2.2
2.5
4.4
6.4
9.0
10.4
15
20
33
40
48
55
Allowable voltage
fluctuation
+ 10%, - 15%
Allowable frequency
fluctuation
±5%
Measures
for power
supply
harmonics
DC Reactor
Optional
12-pulse
Rectification
Not possible
*1 The difference between Heavy Duty ratings and the Normal Duty ratings for the Drive are the rated input and output current, overload capacity, carrier frequency, current limit,
and maximum output frequency. Parameter C6-01 must be set to value of “0” for Heavy Duty ratings and “2” for Normal Duty ratings. Factory default is Heavy Duty (C6-01=0).
*2 Horsepower ratings are based on 230V or 460V NEC Table 430.150. The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual
motor and Drive, be sure that the Drive's rated output current is appropriate for the motor's rated current.
*3 Model 2110 has an overload rating of 138% of rated output current for 60 seconds and a current limit rating of 138%. Models 4220 and 4300 have an overload rating of 150%
of rated output current for 45 seconds and a current limit rating of 150%.
*4 When setting the carrier frequency above the factory default, the Drive must be derated.
*5 Heavy Duty ratings for models 2110, 4220 and 4300 are effective in software version VSF103021 and higher.
*6 Each value shown is the Maximum carrier frequency and default carrier frequency.
*7 The carrier frequency for Heavy Duty is default to 2 kHz. Software version VSF103021 and higher may allow the carrier frequency to be increased above 2 kHz with a