Communications d - 4, Related parameters, Table d.2 serial communication related parameters – Yaskawa F7 Drive User Manual User Manual

Page 223: Important

background image

Communications D - 4

Related Parameters

Modbus communication can perform the following operations regardless of the settings in b1-01 and b1-02:

1. Monitor the operation status of the Drive.

2. Set and read Drive parameters.

3. Reset faults.

4. Input multi-function digital input commands.

5. Control multi-function digital and analog outputs.

Table D.2 Serial Communication Related Parameters

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Control Method

V/F

V/F

w/

PG

Open

Loop

Vector

Flux

Vector

b1-01

Frequency Reference
Selection
Reference Source

Selects the frequency reference input source.
0: Operator - Digital preset speed U1-01 or d1-01 to d1-17.
1: Terminals - Analog input terminal A1 (or terminal A2 based on

parameter H3-13).

2: Serial Com - Modbus RS-422/485 terminals R+, R-, S+, and S-.
3: Option PCB - Option board connected to 2CN.
4: Pulse Input (Terminal RP)

0 to 4

1

Q

Q

Q

Q

b1-02

Run Command Selection
Run Source

Selects the run command input source.
0: Operator - RUN and STOP keys on Digital Operator.
1: Terminals - Contact closure on terminals S1 or S2.
2: Serial Com - Modbus RS-422/485 terminals R+, R-, S+, and S-.
3: Option PCB - Option board connected to 2CN.

0 to 3

1

Q

Q

Q

Q

H5-01

Drive Node Address
Serial Comm Adr

Selects Drive station node number (address) for Modbus terminals
R+, R-, S+, S-. The Drive’s power must be cycled for the setting to
take effect. Set H5-01 to 0 to disable Drive responses to Modbus
communications.

0 to 20

Hex

1F

A

A

A

A

H5-02

Communication Speed
Selection
Serial Baud Rate

Selects the baud rate for Modbus terminals R+, R-, S+ and S-. The
Drive’s power must be cycled for the setting to take effect.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps

0 to 4

3

A

A

A

A

H5-03

Communication Parity
Selection
Serial Com Sel

Selects the communication parity for Modbus terminals R+, R-, S+
and S-. The Drive’s power must be cycled for the setting to take
effect.
0: No Parity
1: Even Parity
2: Odd Parity

0 to 2

0

A

A

A

A

H5-04

Stopping Method After
Communication Error
Serial Fault Sel

Selects the stopping method when a communication timeout fault
(CE) is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
4: Run at d1-04

0 to 3

3

A

A

A

A

H5-05

Communication Fault
Detection Selection
Serial Flt Dtct

Enables or disables the communications timeout fault (CE).
0: Disabled - A communication loss will not cause a
communication fault.
1: Enabled - If communication is lost for more than 2 seconds, a

CE fault will occur.

0 to 10

1

A

A

A

A

H5-06

Drive Transmit Wait Time
Transmit WaitTIM

Set the delay time from when the Drive receives data to when the
Drive sends data.

5 to 65

5ms

A

A

A

A

H5-07

RTS Control Selection
RTS Control Sel

Enables or disables “request to send” (RTS) control:
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)

0 to 1

1

A

A

A

A

IMPORTANT

An OR operation is performed between the multi-function command input from the master device and the
command input from multi-function digital input terminals S3 to S8.