Parameters a - 34, Hunting prevention, Afr tuning – Yaskawa F7 Drive User Manual User Manual

Page 199: Table a.1 f7 parameter list (continued)

background image

Parameters A - 34

L8-07

Output Phase Loss
Protection
Ph Loss Out Sel

Selects the detection of output current open-phase.
When applied motor capacity is too small for Drive capacity,
output phase loss may be detected inadvertently. In this case, set to
0.

0: Disabled
1: 1-phase Loss Detection
2: 2/3-phase Loss Detection

0 to 1

1

A

A

A

A

L8-09

Output Ground Fault
Detection Selection
Ground Fault Sel

Enables and disables the Drive’s output ground fault detection.
0: Disabled
1: Enabled

0 to 1

1

A

A

A

A

L8-10

Heatsink Cooling Fan
Operation Selection
Fan On/Off Sel

Controls the heatsink cooling fan operation.
0: Fan On-Run Mode - Fan will operate only when the Drive is

running and for L8-11 seconds after RUN is removed.

1: Fan Always On

- Cooling fan operates whenever the Drive is

powered up.)

0 to 1

0

A

A

A

A

L8-11

Heatsink Cooling Fan
Operation Delay Time
Fan Delay Time

This parameter sets the delay time for the cooling fan turn off after
the run command is removed when L8-10 = 0.

0 to 300

60sec

A

A

A

A

L8-12

Ambient Temperature
Setting
Ambient Temp

When the Drive is installed in an ambient temperature exceeding its
rating, the Drive overload (OL2) protection level is adjusted.

45 to 60

45°C

A

A

A

A

L8-15

OL2 Characteristic
Selection at Low Speeds
OL2 Sel @ L-Spd

This parameter assists in protecting the output transistors from
overheating when output current is high and output frequency is
low (6Hz and less).
0: Disabled
1: Enabled (L8-18 is active)

0 to 1

0

A

A

A

A

L8-18

Soft CLA Selection
Soft CLA Sel

Enables and disables the software current limit function. Consult
the factory before disabling.
0: Disabled
1: Enabled

0 to 1

1

A

A

A

A

L8-32

<3021>

Cooling Fan OH1
Detection
OH1 Detect Sel

0: Disabled (FAN minor fault detection)
1: Enabled (OH1 major fault detection)

0, 1

1

A

A

A

A

Hunting Prevention

n1-01

Hunting Prevention
Selection
Hunt Prev Select

If the motor vibrates while lightly loaded, hunting
prevention may reduce the vibration.
0: Disabled
1: Enabled

0 to 1

1

A

A

-

-

n1-02

Hunting Prevention Gain
Setting
Hunt Prev Gain

Sets the gain for the Hunting Prevention Function.
If the motor vibrates while lightly loaded and n1-01=1, increase the
gain by 0.1 until vibration ceases.
If the motor stalls while n1-01=1, decrease the gain by 0.1 until the
stalling ceases.

0.00 to

2.50

1.00

A

A

-

-

AFR Tuning

n2-01

Speed Feedback
Detection Control
(AFR) Gain
AFR Gain

Sets the internal speed feedback detection control gain in the
automatic frequency regulator (AFR).
Normally, there is no need to change this setting.
Adjust this parameter as follows:
• If hunting occurs, increase the set value.
• If response is low, decrease the set value.
Adjust the setting by 0.05 units at a time, while checking the
response.

0.00 to

10.00

1.00

-

-

A

-

n2-02

Speed Feedback
Detection Control (AFR)
Time Constant
AFR Time

Sets the time constant to control the rate of change in the speed
feedback detection control.

0 to 2000

50ms

-

-

A

-

n2-03

Speed Feedback
Detection Control (AFR)
Time Constant 2
AFR Time 2

Sets the time constant to control the amount of change in the speed
at low speed.

0 to 2000

750ms

-

-

A

-

Denotes that parameter can be changed when the Drive is running.

Table A.1 F7 Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Control Method

V/F

V/F

w/PG

Open

Loop

Vector

Flux

Vector