Basic Programming 5 - 12
Input Voltage Setting
E1-01 Input Voltage Setting
Setting Range:
155.0V to 255.0V (240V Models)
310.0V to 510.0V (480V Models)
Factory Defaults: 230.0V (240V Models)
460.0V (480V Models)
Set the Input Voltage parameter (E1-01) to the nominal voltage of the connected AC power supply. This parameter adjusts the
levels of some protective features of the Drive (i.e. Overvoltage, Built-in Braking Transistor Turn-on, Stall Prevention, etc.).
E1-01 also serves as the Maximum/Base Voltage used by the Preset V/F curves (E1-03=0 to E).
DRIVE INPUT VOLTAGE (NOT MOTOR VOLTAGE) MUST BE SET IN E1-01 FOR THE PRO-
TECTIVE FEATURES OF THE DRIVE TO FUNCTION PROPERLY. FAILURE TO DO SO
MAY RESULT IN EQUIPMENT DAMAGE AND/OR PERSONAL INJURY.
V/F Pattern
E1-03 V/F Pattern Selection
Setting
Description
0
50Hz
1
60Hz
2
60Hz (with 50Hz Base)
3
72Hz (with 60Hz Base)
4
50Hz VT1
5
50Hz VT2
6
60Hz VT1
7
60Hz VT2
8
50Hz HST1
9
50Hz HST2
A
60Hz HST1
B
60Hz HST2
C
90Hz (with 60Hz Base)
D
120Hz (with 60Hz Base)
E
180Hz (with 60Hz Base)
F
Custom V/F (factory default)
FF
Custom w/o limit
Note: VT = Variable Torque, HST = High Starting Torque
WARNING