Diagnostics & Troubleshooting 6 - 17

Auto-Tuning Faults

Auto-Tuning faults are shown below. When the following faults are detected, the fault is displayed on the Digital Operator and
the motor coasts to a stop. No fault or alarm outputs will occur.

Table 6.4 Auto-Tuning Fault Displays and Processing

Digital Operator

Display

Description

Probable Cause

Corrective Action

Er - 01

Fault

Motor Data Fault

•There is an error in the data input

for Auto-Tuning.

•There is an error in the relationship

between the motor output and the
motor rated current.

•There is an error between the no-

load current setting and the input
motor rated current (when Auto-
Tuning only line-to-line

resistance is performed for vector

control).

• Check Auto-Tuning input data (T1

parameters).

• Check Drive and motor capacity

for compatibility.

• Check motor rated current and

no-load current (E2-03 and
T1-04).

Er - 02

Minor Fault

Alarm

An alarm is detected during Auto-
Tuning.

• Check Auto-Tuning input data (T1

parameters).

• Check output/motor wiring.
• Check the load.

Er - 03

STOP key

STOP Key Input

The STOP key is pressed during
Auto-Tuning, and the Auto-Tuning is
interrupted.

Er - 04

Resistance

Line-to-Line Resistance Fault

Auto-Tuning is not completed within
the specified time.
The Auto-Tuning result is outside the
parameter setting range.

• Check Auto-Tuning input data (T1

parameters).

• Check motor wiring.
• If the motor and the machine are

connected, disconnect the motor
from the machine.

• For Er-08, if the setting of T1-03 is

higher than the Drive’s input
voltage, change the input voltage
setting.

Er - 05

No-Load Current

No-Load Current Fault

Er - 08

Rated Slip

Rated Slip Fault

Er - 09

Accelerate

Acceleration Fault
Detected only for rotational Auto-
Tuning.

The motor did not accelerate in the
specified time (C1-01 + 10 seconds).

• Increase C1-01 (Accel Time 1)
• Increase L7-01 and L7-02

(Forward/Reverse Torque Limits)

if they are low.

• If the motor and load are

connected, disconnect the motor
from the load.

Er - 11

Motor Speed

Motor Speed Fault
Detected only for rotational Auto-
Tuning.

The torque reference exceeded 100%
during acceleration. Detected when
A1-02 = 2 or 3 (vector control).

• Increase C1-01 (Accel Time 1)
• Check the input data [particularly

the number of PG pulses (F1-01)
and the number of motor poles
(E2-04)].

• If the motor and load are

connected, disconnect the motor
from the load.