beautypg.com

Diagnostics & troubleshooting 6 - 4 – Yaskawa F7 Drive User Manual User Manual

Page 129

background image

Diagnostics & Troubleshooting 6 - 4

Table 6.1 Fault Displays and Processing (continued)

Digital

Operator Display

Description

Cause

Corrective Action

DEV

Speed Deviation

Excessive Speed Deviation
Detected when F1-04 = 0 to 2 and in Flux
Vector control method A1-02 = 3.
The speed deviation is greater than the
setting in F1-10 for a time longer than the
setting in F1-11.

The load is locked.

Reduce the load.

The acceleration or
deceleration time is too short.

Lengthen the acceleration time
and deceleration time.

The load is too large.

Check the mechanical system.

The settings in F1-10 and
F1-11 are not appropriate for
the application.

Check the settings in F1-10 and
F1-11.

Braking mechanism is
engaged

Check that the brake is released
when using brake (motor).

Encoder wiring and/or encoder
settings (F1 group) are
incorrect

Check for proper encoder wiring
and verify the parameter settings
are correct.

EF0

Opt External Flt

Option Board External Fault

An external fault condition is
present.

Check for an external condition.

Verify the parameters.

Verify communication signal.

EF3

Ext Fault S3

External Fault at Terminal S3 - S8
Detected when terminals S3 - S8 (H1-01 to
H1-06) are programmed for external fault
function that stops the Drive using ramp to
stop, coast to stop, or fast stop.

An external fault condition is
present that is connected to a
multi-function digital input.

Eliminate the cause of the
external fault condition.

EF4

Ext Fault S4

EF5

Ext Fault S5

EF6

Ext Fault S6

EF7

Ext Fault S7

EF8

Ext Fault S8

E5

SI-T WDT Err

<3021>

SI-T Watchdog Error
Consistency error of received control data.

Synchronization error between
master controller and Drive for
control data.

Check the communications
timing such as communications
cycle.
Refer to SI-T manual for details.

E-15

SI-F/G Com Err

SI-F/G Communication Error Detected
A communication error is detected when a run
command or frequency reference is set from
the SI-F/G Option Card (b1-01=3, b1-02=3)
and communication is lost.

Communication has been lost
to the SI-F/G option card
connected and b1-01=3 and/or
b1-02=3.

Check the communication
signals.

Check the settings of b1-01 and
b1-02.

Check the setting of F6-01.

Check the host side (master)
communication configuration.