Capacity Related Parameters B - 2

Drive Capacity Selection

Parameter o2-04 sets the Drive capacity according to the model number. Parameter o2-04 needs to be adjusted only when
replacing a control board. Do not change the o2-04 setting for any other reason.

If the Drive’s control board is replaced, the next time the Drive is powered up, parameter o2-04 must be set to the appropriate
value listed in Table B.1 for the Drive model number. This will automatically program the values of all other parameters listed
in Table B.2 to the factory settings for that particular Drive rating.

Table B.1 Drive Capacity Selection

Voltage

F7 Model Number

o2-04 Setting

208-240Vac

CIMR-F7U20P4

0

CIMR-F7U20P7

1

CIMR-F7U21P5

2

CIMR-F7U22P2

3

CIMR-F7U23P7

4

CIMR-F7U25P5

5

CIMR-F7U27P5

6

CIMR-F7U2011

7

CIMR-F7U2015

8

CIMR-F7U2018

9

CIMR-F7U2022

A

CIMR-F7U2030

B

208-230Vac

CIMR-F7U2037

C

CIMR-F7U2045

D

CIMR-F7U2055

E

CIMR-F7U2075

F

CIMR-F7U2090

10

CIMR-F7U2110

11

480Vac

CIMR-F7U40P4

20

CIMR-F7U40P7

21

CIMR-F7U41P5

22

CIMR-F7U42P2

23

CIMR-F7U43P7

24

CIMR-F7U44P0

25

CIMR-F7U45P5

26

CIMR-F7U47P5

27

CIMR-F7U4011

28

CIMR-F7U4015

29

CIMR-F7U4018

2A

CIMR-F7U4022

2B

CIMR-F7U4030

2C

CIMR-F7U4037

2D

CIMR-F7U4045

2E

CIMR-F7U4055

2F

CIMR-F7U4075

30

CIMR-F7U4090

31

CIMR-F7U4110

32

CIMR-F7U4132

33

CIMR-F7U4160

34

CIMR-F7U4185

35

CIMR-F7U4220

36

CIMR-F7U4300

37