Capacity Related Parameters B - 2
Drive Capacity Selection
Parameter o2-04 sets the Drive capacity according to the model number. Parameter o2-04 needs to be adjusted only when
replacing a control board. Do not change the o2-04 setting for any other reason.
If the Drive’s control board is replaced, the next time the Drive is powered up, parameter o2-04 must be set to the appropriate
value listed in Table B.1 for the Drive model number. This will automatically program the values of all other parameters listed
in Table B.2 to the factory settings for that particular Drive rating.
Table B.1 Drive Capacity Selection
Voltage
F7 Model Number
o2-04 Setting
208-240Vac
CIMR-F7U20P4
0
CIMR-F7U20P7
1
CIMR-F7U21P5
2
CIMR-F7U22P2
3
CIMR-F7U23P7
4
CIMR-F7U25P5
5
CIMR-F7U27P5
6
CIMR-F7U2011
7
CIMR-F7U2015
8
CIMR-F7U2018
9
CIMR-F7U2022
A
CIMR-F7U2030
B
208-230Vac
CIMR-F7U2037
C
CIMR-F7U2045
D
CIMR-F7U2055
E
CIMR-F7U2075
F
CIMR-F7U2090
10
CIMR-F7U2110
11
480Vac
CIMR-F7U40P4
20
CIMR-F7U40P7
21
CIMR-F7U41P5
22
CIMR-F7U42P2
23
CIMR-F7U43P7
24
CIMR-F7U44P0
25
CIMR-F7U45P5
26
CIMR-F7U47P5
27
CIMR-F7U4011
28
CIMR-F7U4015
29
CIMR-F7U4018
2A
CIMR-F7U4022
2B
CIMR-F7U4030
2C
CIMR-F7U4037
2D
CIMR-F7U4045
2E
CIMR-F7U4055
2F
CIMR-F7U4075
30
CIMR-F7U4090
31
CIMR-F7U4110
32
CIMR-F7U4132
33
CIMR-F7U4160
34
CIMR-F7U4185
35
CIMR-F7U4220
36
CIMR-F7U4300
37