Basic Programming 5 - 23

Stall Prevention

L3-04 Stall Prevention During Deceleration Selection

The stall prevention during deceleration function adjusts the deceleration time in order to prevent OV fault trips during
deceleration. If L3-04=0, stall prevention is disabled, and if the load is large and the deceleration time short enough, the Drive
may fault and stop.

If L3-04=1, the standard stall prevention function is enabled. If, during deceleration, the DC Bus voltage exceeds the stall
prevention level (see table below), the Drive will discontinue decelerating and maintain speed. Once the DC Bus voltage has
dropped below the stall prevention level, deceleration will continue. Fig 5.11 demonstrates deceleration when L3-04=1.

Fig 5.11 Stall Prevention

Setting

Description

0

Disabled

1

General purpose (Enabled) (factory default)

2

Intelligent stall prevention (Enabled)

3

Stall prevention with DB resistor (Enabled)

Drive Voltage

Stall Prevention Level during Deceleration

240Vac

380Vdc

480Vac

E1-01

≥ 400Vac

760Vdc

E1-01

< 400Vac

660Vdc

a

b

Output
Frequency

DC Bus
Voltage

a

b

a - Set decel time
b - Decel time is extended

380/660/760Vdc

t